EA-440AE8-C01 C
20.34 kW
Defrost: Electric
Product code: EA-245AG6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,352 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 76.7 m² |
| Inner volume | 22.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 115 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-245AG6-C01 C | None |
|---|---|
| EA-245AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.88 | 8.87 | 8.89 | 8.92 | 8.88 | 8.78 | 8.63 | 8.86 | 9.43 | 10.22 | 9.97 | 9.89 | 9.79 | 9.65 |
| 5 | 11.25 | 11.40 | 11.54 | 11.66 | 11.67 | 11.57 | 11.38 | 11.58 | 12.29 | 13.30 | 12.86 | 12.71 | 12.51 | 12.21 |
| 6 | 13.60 | 13.92 | 14.22 | 14.45 | 14.54 | 14.47 | 14.27 | 14.43 | 15.28 | 16.51 | 15.89 | 15.65 | 15.30 | 14.74 |
| 7 | 15.74 | 16.31 | 16.82 | 17.25 | 17.45 | 17.45 | 17.24 | 17.38 | 18.38 | 19.85 | 19.09 | 18.78 | 18.31 | 17.50 |
| 8 | 17.64 | 18.43 | 19.15 | 19.77 | 20.14 | 20.21 | 20.15 | 20.36 | 21.54 | 23.23 | 22.37 | 21.99 | 21.39 | 20.38 |
| 9 | 19.38 | 20.43 | 21.39 | 22.11 | 22.61 | 22.85 | 22.83 | 23.06 | 24.42 | 26.39 | 25.56 | 25.15 | 24.52 | 23.33 |
| 10 | 20.98 | 22.18 | 23.42 | 24.47 | 25.13 | 25.47 | 25.52 | 25.78 | 27.30 | 29.49 | 28.58 | 28.12 | 27.39 | 26.10 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 28.577 |
| SC2 | 0 | 8 | 20.361 |
| SC3 | -18 | 7 | 17.356 |
| SC4 | -25 | 6 | 14.224 |
| SC5 | -34 | 6 | 13.685 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.