EA-540AE6-C01 C
29.91 kW
Defrost: Electric
Product code: EA-263EE4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,900 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 200.5 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 216 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EE4-C01 C | None |
|---|---|
| EA-263EE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.85 | 12.90 | 12.98 | 13.07 | 13.08 | 13.02 | 12.91 | 13.16 | 14.01 | 15.19 | 14.88 | 14.78 | 14.64 | 14.42 |
| 5 | 16.25 | 16.51 | 16.75 | 16.97 | 17.03 | 16.95 | 16.81 | 17.03 | 18.08 | 19.58 | 19.06 | 18.89 | 18.63 | 18.27 |
| 6 | 19.43 | 20.02 | 20.53 | 20.95 | 21.07 | 21.08 | 20.93 | 21.12 | 22.39 | 24.21 | 23.50 | 23.24 | 22.85 | 22.25 |
| 7 | 22.40 | 23.25 | 24.10 | 24.81 | 25.19 | 25.32 | 25.23 | 25.41 | 26.92 | 29.12 | 28.23 | 27.87 | 27.35 | 26.51 |
| 8 | 24.87 | 26.16 | 27.32 | 28.33 | 28.98 | 29.33 | 29.42 | 29.73 | 31.55 | 34.18 | 33.14 | 32.71 | 32.06 | 31.00 |
| 9 | 27.19 | 28.89 | 30.42 | 31.74 | 32.62 | 33.10 | 33.29 | 33.65 | 35.71 | 38.71 | 37.72 | 37.28 | 36.63 | 35.53 |
| 10 | 29.32 | 31.45 | 33.38 | 35.05 | 36.17 | 36.86 | 37.16 | 37.60 | 39.90 | 43.24 | 42.16 | 41.67 | 40.92 | 39.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.161 |
| SC2 | 0 | 8 | 29.734 |
| SC3 | -18 | 7 | 24.995 |
| SC4 | -25 | 6 | 20.532 |
| SC5 | -34 | 6 | 19.587 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.