EA-250AG10-C09 C
23.12 kW
Defrost: Electric
Product code: EA-345AE8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,615 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 66.5 m² |
| Inner volume | 25.0 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-345AE8-C01 C | None |
|---|---|
| EA-345AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.39 | 9.48 | 9.56 | 9.61 | 9.57 | 9.46 | 9.30 | 9.44 | 10.02 | 10.80 | 10.46 | 10.33 | 10.14 | 9.86 |
| 5 | 12.05 | 12.38 | 12.62 | 12.85 | 12.94 | 12.89 | 12.74 | 12.90 | 13.67 | 14.76 | 14.28 | 14.12 | 13.89 | 13.57 |
| 6 | 14.46 | 15.10 | 15.65 | 16.14 | 16.40 | 16.47 | 16.36 | 16.53 | 17.53 | 18.95 | 18.34 | 18.11 | 17.75 | 17.21 |
| 7 | 16.51 | 17.41 | 18.22 | 18.84 | 19.31 | 19.59 | 19.69 | 19.97 | 21.22 | 23.05 | 22.47 | 22.25 | 21.87 | 21.18 |
| 8 | 18.37 | 19.59 | 20.56 | 21.52 | 22.19 | 22.60 | 22.80 | 23.14 | 24.58 | 26.71 | 26.07 | 25.80 | 25.39 | 24.70 |
| 9 | 20.06 | 21.47 | 22.88 | 24.12 | 25.02 | 25.58 | 25.90 | 26.32 | 27.97 | 30.40 | 29.72 | 29.41 | 28.93 | 28.11 |
| 10 | ≈ 21.29 | 23.33 | 25.08 | 26.61 | 27.75 | 28.53 | 28.97 | 29.50 | 31.37 | 34.11 | 33.39 | 33.04 | 32.51 | 31.58 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.390 |
| SC2 | 0 | 8 | 23.135 |
| SC3 | -18 | 7 | 19.055 |
| SC4 | -25 | 6 | 15.653 |
| SC5 | -34 | 6 | 14.618 |
| A | 2467 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.