EA-250AE10-C09 C
19.23 kW
Defrost: Electric
Product code: EA-435AG6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,593 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 87.7 m² |
| Inner volume | 25.7 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-435AG6-C01 C | None |
|---|---|
| EA-435AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.46 | 8.47 | 8.51 | 8.55 | 8.53 | 8.46 | 8.33 | 8.55 | 9.11 | 9.88 | 9.64 | 9.57 | 9.47 | 9.34 |
| 5 | 10.66 | 10.80 | 10.95 | 11.08 | 11.11 | 11.04 | 10.89 | 11.06 | 11.74 | 12.71 | 12.30 | 12.16 | 11.96 | 11.65 |
| 6 | 12.84 | 13.14 | 13.39 | 13.65 | 13.75 | 13.72 | 13.56 | 13.70 | 14.51 | 15.69 | 15.13 | 14.91 | 14.58 | 14.06 |
| 7 | 14.84 | 15.35 | 15.83 | 16.23 | 16.43 | 16.44 | 16.29 | 16.41 | 17.37 | 18.76 | 18.09 | 17.81 | 17.38 | 16.66 |
| 8 | 16.67 | 17.40 | 18.07 | 18.66 | 19.02 | 19.15 | 19.06 | 19.18 | 20.29 | 21.87 | 21.12 | 20.78 | 20.26 | 19.34 |
| 9 | 18.30 | 19.28 | 20.17 | 20.95 | 21.33 | 21.57 | 21.58 | 21.80 | 23.09 | 24.96 | 24.20 | 23.80 | 23.19 | 22.10 |
| 10 | 19.82 | 21.06 | 22.08 | 23.06 | 23.68 | 24.02 | 24.09 | 24.34 | 25.78 | 27.86 | 27.04 | 26.64 | 26.00 | 24.86 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.040 |
| SC2 | 0 | 8 | 19.183 |
| SC3 | -18 | 7 | 16.334 |
| SC4 | -25 | 6 | 13.388 |
| SC5 | -34 | 6 | 12.921 |
| A | 2357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.