EA-163FC7-C19 C
11.78 kW
Defrost: Electric
Product code: EA-530AE6-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,845 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 55.8 m² |
| Inner volume | 15.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-530AE6-C05 C | None |
|---|---|
| EA-530AE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.14 | 5.16 | 5.20 | 5.24 | 5.23 | 5.20 | 5.13 | 5.25 | 5.60 | 6.07 | 5.92 | 5.88 | 5.82 | 5.74 |
| 5 | 6.46 | 6.57 | 6.68 | 6.78 | 6.81 | 6.78 | 6.71 | 6.81 | 7.22 | 7.82 | 7.58 | 7.49 | 7.36 | 7.17 |
| 6 | 7.76 | 7.98 | 8.18 | 8.34 | 8.42 | 8.42 | 8.35 | 8.43 | 8.93 | 9.67 | 9.34 | 9.21 | 9.02 | 8.72 |
| 7 | 8.95 | 9.30 | 9.63 | 9.90 | 10.05 | 10.09 | 10.02 | 10.11 | 10.70 | 11.57 | 11.19 | 11.03 | 10.80 | 10.41 |
| 8 | 10.02 | 10.50 | 10.94 | 11.33 | 11.58 | 11.69 | 11.67 | 11.79 | 12.49 | 13.49 | 13.07 | 12.89 | 12.61 | 12.13 |
| 9 | 10.98 | 11.62 | 12.20 | 12.65 | 12.97 | 13.15 | 13.20 | 13.35 | 14.15 | 15.31 | 14.91 | 14.72 | 14.42 | 13.89 |
| 10 | 11.87 | 12.68 | 13.34 | 13.97 | 14.39 | 14.64 | 14.72 | 14.90 | 15.80 | 17.10 | 16.66 | 16.45 | 16.11 | 15.53 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.658 |
| SC2 | 0 | 8 | 11.793 |
| SC3 | -18 | 7 | 9.975 |
| SC4 | -25 | 6 | 8.179 |
| SC5 | -34 | 6 | 7.818 |
| A | 2407 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.