EA-263EE7-C06 C
26.17 kW
Defrost: None
Product code: EA-540AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,023 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 97.6 m² |
| Inner volume | 20.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 133 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-540AC4-C01 C | None |
|---|---|
| EA-540AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.01 | 10.85 | 10.76 | 10.70 | 10.59 | 10.46 | 10.30 | 10.50 | 11.14 | 12.02 | 11.71 | 11.60 | 11.45 | 11.21 |
| 5 | 14.39 | 14.38 | 14.40 | 14.42 | 14.33 | 14.15 | 13.92 | 14.10 | 14.95 | 16.14 | 15.68 | 15.52 | 15.30 | 14.99 |
| 6 | 17.79 | 18.02 | 18.24 | 18.41 | 18.37 | 18.21 | 17.94 | 18.08 | 19.14 | 20.64 | 19.94 | 19.69 | 19.35 | 18.85 |
| 7 | 20.71 | 21.21 | 21.70 | 22.15 | 22.38 | 22.44 | 22.24 | 22.32 | 23.60 | 25.47 | 24.56 | 24.23 | 23.73 | 22.96 |
| 8 | 23.37 | 24.17 | 24.81 | 25.46 | 25.84 | 25.99 | 25.96 | 26.19 | 27.77 | 30.10 | 29.25 | 28.90 | 28.41 | 27.45 |
| 9 | 25.86 | 26.89 | 27.91 | 28.80 | 29.35 | 29.62 | 29.62 | 29.89 | 31.68 | 34.32 | 33.36 | 32.95 | 32.35 | 31.37 |
| 10 | 28.07 | 29.57 | 30.92 | 32.09 | 32.82 | 33.22 | 33.31 | 33.63 | 35.66 | 38.61 | 37.55 | 37.08 | 36.38 | 35.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 37.548 |
| SC2 | 0 | 8 | 26.192 |
| SC3 | -18 | 7 | 22.262 |
| SC4 | -25 | 6 | 18.236 |
| SC5 | -34 | 6 | 17.863 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.