EA-463GG4-C13 C
141.75 kW
Defrost: None
Product code: EA-563FG4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 64,354 m³/h |
|---|---|
| Air throw | 39 m |
| External surface | 835.3 m² |
| Inner volume | 166.7 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 769 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FG4-C08 C | None |
|---|---|
| EA-563FG4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 62.25 | 63.17 | 64.02 | 64.76 | 64.83 | 64.57 | 63.93 | 65.21 | 69.37 | 75.17 | 73.48 | 72.91 | 72.12 | 71.02 |
| 5 | 77.43 | 79.86 | 81.97 | 83.30 | 84.09 | 84.08 | 83.39 | 84.58 | 89.77 | 97.15 | 94.46 | 93.49 | 92.12 | 90.06 |
| 6 | 90.78 | 95.04 | 98.68 | 101.86 | 103.70 | 104.25 | 103.76 | 104.91 | 111.25 | 120.43 | 116.75 | 115.32 | 113.22 | 109.85 |
| 7 | 102.85 | 108.61 | 113.80 | 118.29 | 121.19 | 122.73 | 123.07 | 124.63 | 132.30 | 143.57 | 139.72 | 138.17 | 135.46 | 130.97 |
| 8 | 113.68 | 121.34 | 128.30 | 134.31 | 138.36 | 140.67 | 141.38 | 143.17 | 151.95 | 164.80 | 160.40 | 158.52 | 155.64 | 150.79 |
| 9 | ≈ 123.52 | 133.22 | 142.11 | 149.85 | 155.22 | 158.38 | 159.72 | 161.83 | 171.76 | 186.23 | 181.39 | 179.18 | 175.81 | 170.01 |
| 10 | ≈ 132.40 | 144.20 | 155.17 | 164.79 | 171.57 | 175.94 | 177.98 | 180.55 | 191.67 | 207.82 | 202.59 | 200.11 | 196.27 | not rated |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 54.78 | 58.30 | 63.24 | 61.86 | 61.40 | 60.76 | 59.86 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | 97.45 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | 110.18 | 114.25 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | 122.46 | 127.72 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | 134.19 | 140.84 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 202.592 | — |
| SC2 | 0 | 8 | 143.168 | — |
| SC3 | -18 | 7 | 119.629 | — |
| SC4 | -25 | 6 | 98.680 | — |
| SC5 | -34 | 6 | 91.960 | — |
| A | 5415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1135 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.