EA-245AC7-C01 C
12.93 kW
Defrost: Electric
Product code: EA-630BE8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,751 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 46.2 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 91 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 73.6 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-630BE8-C01 C | None |
|---|---|
| EA-630BE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.38 | 5.41 | 5.45 | 5.48 | 5.47 | 5.42 | 5.35 | 5.44 | 5.79 | 6.26 | 6.09 | 6.04 | 5.97 | 5.84 |
| 5 | 6.82 | 6.97 | 7.11 | 7.22 | 7.26 | 7.24 | 7.16 | 7.25 | 7.69 | 8.32 | 8.06 | 7.96 | 7.83 | 7.65 |
| 6 | 8.23 | 8.51 | 8.77 | 9.00 | 9.09 | 9.12 | 9.07 | 9.15 | 9.70 | 10.49 | 10.15 | 10.02 | 9.82 | 9.51 |
| 7 | 9.48 | 9.92 | 10.32 | 10.68 | 10.91 | 11.03 | 11.02 | 11.11 | 11.76 | 12.73 | 12.34 | 12.18 | 11.92 | 11.49 |
| 8 | 10.58 | 11.17 | 11.73 | 12.15 | 12.48 | 12.67 | 12.75 | 12.92 | 13.72 | 14.89 | 14.52 | 14.34 | 14.06 | 13.53 |
| 9 | 11.58 | 12.36 | 12.99 | 13.62 | 14.04 | 14.32 | 14.45 | 14.66 | 15.57 | 16.89 | 16.49 | 16.28 | 15.97 | 15.41 |
| 10 | 12.49 | 13.38 | 14.26 | 15.03 | 15.59 | 15.95 | 16.14 | 16.40 | 17.42 | 18.91 | 18.47 | 18.24 | 17.88 | 17.25 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.470 |
| SC2 | 0 | 8 | 12.918 |
| SC3 | -18 | 7 | 10.787 |
| SC4 | -25 | 6 | 8.774 |
| SC5 | -34 | 6 | 8.298 |
| A | 2557 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.