EB-330AC7-B01 C
5.64 kW
Defrost: Electric
Product code: EB-140AC4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,342 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 19.1 m² |
| Inner volume | 3.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-140AC4-B01 C | None |
|---|---|
| EB-140AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.34 | 2.38 | 2.41 | 2.44 | 2.44 | 2.43 | 2.41 | 2.44 | 2.59 | 2.80 | 2.73 | 2.70 | 2.67 | 2.61 |
| 5 | 2.96 | 3.06 | 3.16 | 3.23 | 3.27 | 3.28 | 3.26 | 3.29 | 3.49 | 3.77 | 3.67 | 3.63 | 3.58 | 3.50 |
| 6 | 3.48 | 3.64 | 3.79 | 3.92 | 4.00 | 4.05 | 4.07 | 4.13 | 4.38 | 4.76 | 4.66 | 4.62 | 4.56 | 4.45 |
| 7 | 3.99 | 4.22 | 4.42 | 4.60 | 4.71 | 4.79 | 4.83 | 4.89 | 5.20 | 5.64 | 5.52 | 5.47 | 5.39 | 5.27 |
| 8 | 4.44 | 4.75 | 5.02 | 5.26 | 5.43 | 5.54 | 5.60 | 5.67 | 6.02 | 6.55 | 6.39 | 6.33 | 6.25 | 6.10 |
| 9 | 4.85 | 5.24 | 5.59 | 5.91 | 6.13 | 6.25 | 6.34 | 6.44 | 6.84 | 7.44 | 7.29 | 7.22 | 7.12 | 6.94 |
| 10 | ≈ 5.22 | 5.69 | 6.14 | 6.48 | 6.77 | 6.97 | 7.09 | 7.22 | 7.68 | 8.35 | 8.19 | 8.12 | 8.01 | 7.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.194 |
| SC2 | 0 | 8 | 5.667 |
| SC3 | -18 | 7 | 4.658 |
| SC4 | -25 | 6 | 3.787 |
| SC5 | -34 | 6 | 3.517 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.