EB-430AC4-B01 C
9.10 kW
Defrost: Electric
Product code: EB-240AC7-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,005 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 24.2 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 62 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-240AC7-B01 C | None |
|---|---|
| EB-240AC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.71 | 3.72 | 3.74 | 3.75 | 3.74 | 3.70 | 3.65 | 3.67 | 3.89 | 4.19 | 4.06 | 4.01 | 3.95 | 3.84 |
| 5 | 4.76 | 4.86 | 4.96 | 5.04 | 5.07 | 5.06 | 5.02 | 5.04 | 5.34 | 5.76 | 5.58 | 5.52 | 5.43 | 5.29 |
| 6 | 5.72 | 5.91 | 6.10 | 6.27 | 6.39 | 6.46 | 6.46 | 6.50 | 6.89 | 7.45 | 7.23 | 7.15 | 7.03 | 6.84 |
| 7 | 6.56 | 6.85 | 7.13 | 7.38 | 7.55 | 7.66 | 7.71 | 7.80 | 8.29 | 9.00 | 8.81 | 8.73 | 8.61 | 8.42 |
| 8 | 7.40 | 7.80 | 8.16 | 8.49 | 8.73 | 8.86 | 8.96 | 9.07 | 9.63 | 10.47 | 10.25 | 10.16 | 10.03 | 9.80 |
| 9 | 8.13 | 8.65 | 9.13 | 9.57 | 9.88 | 10.09 | 10.22 | 10.34 | 10.99 | 11.95 | 11.70 | 11.60 | 11.45 | 11.19 |
| 10 | 8.80 | 9.46 | 10.06 | 10.60 | 11.00 | 11.23 | 11.42 | 11.60 | 12.34 | 13.42 | 13.18 | 13.07 | 12.90 | 12.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.177 |
| SC2 | 0 | 8 | 9.065 |
| SC3 | -18 | 7 | 7.455 |
| SC4 | -25 | 6 | 6.101 |
| SC5 | -34 | 6 | 5.768 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.