EB-430BB4-B01 C
8.77 kW
Defrost: Electric
Product code: EB-330BE6-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,775 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 32.0 m² |
| Inner volume | 7.7 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.4 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-330BE6-B01 C | None |
|---|---|
| EB-330BE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.78 | 3.85 | 3.91 | 3.97 | 4.00 | 4.00 | 3.97 | 4.03 | 4.28 | 4.64 | 4.52 | 4.48 | 4.43 | 4.35 |
| 5 | 4.70 | 4.85 | 4.99 | 5.11 | 5.18 | 5.20 | 5.18 | 5.24 | 5.56 | 6.03 | 5.86 | 5.79 | 5.70 | 5.55 |
| 6 | 5.55 | 5.79 | 6.01 | 6.21 | 6.34 | 6.42 | 6.43 | 6.50 | 6.89 | 7.47 | 7.27 | 7.18 | 7.05 | 6.84 |
| 7 | 6.30 | 6.64 | 6.94 | 7.22 | 7.41 | 7.52 | 7.57 | 7.67 | 8.15 | 8.85 | 8.64 | 8.55 | 8.41 | 8.17 |
| 8 | 7.06 | 7.49 | 7.89 | 8.24 | 8.46 | 8.62 | 8.70 | 8.82 | 9.37 | 10.17 | 9.93 | 9.83 | 9.66 | 9.38 |
| 9 | 7.71 | 8.26 | 8.76 | 9.21 | 9.53 | 9.73 | 9.83 | 9.97 | 10.59 | 11.50 | 11.25 | 11.13 | 10.94 | 10.59 |
| 10 | 8.30 | 8.97 | 9.60 | 10.15 | 10.55 | 10.82 | 10.97 | 11.11 | 11.80 | 12.81 | 12.54 | 12.41 | 12.20 | 11.83 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.542 |
| SC2 | 0 | 8 | 8.819 |
| SC3 | -18 | 7 | 7.306 |
| SC4 | -25 | 6 | 6.007 |
| SC5 | -34 | 6 | 5.606 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.