EB-445AC7-B01 C
21.23 kW
Defrost: Electric
Product code: EB-340AE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,057 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 86.3 m² |
| Inner volume | 15.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-340AE4-B01 C | None |
|---|---|
| EB-340AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.99 | 9.25 | 9.49 | 9.69 | 9.79 | 9.79 | 9.71 | 9.92 | 10.56 | 11.45 | 11.17 | 11.08 | 10.95 | 10.76 |
| 5 | 11.09 | 11.57 | 12.01 | 12.40 | 12.64 | 12.76 | 12.72 | 12.93 | 13.73 | 14.89 | 14.47 | 14.31 | 14.08 | 13.70 |
| 6 | 12.90 | 13.62 | 14.27 | 14.84 | 15.21 | 15.42 | 15.47 | 15.72 | 16.70 | 18.15 | 17.68 | 17.50 | 17.21 | 16.74 |
| 7 | 14.71 | 15.67 | 16.54 | 17.30 | 17.82 | 18.08 | 18.19 | 18.46 | 19.61 | 21.29 | 20.74 | 20.51 | 20.14 | 19.53 |
| 8 | 16.25 | 17.49 | 18.64 | 19.64 | 20.34 | 20.75 | 20.94 | 21.17 | 22.48 | 24.41 | 23.81 | 23.53 | 23.10 | 22.35 |
| 9 | ≈ 17.65 | 19.20 | 20.64 | 21.91 | 22.66 | 23.25 | 23.55 | 23.94 | 25.43 | 27.60 | 26.93 | 26.61 | 26.12 | 25.24 |
| 10 | ≈ 18.90 | 20.76 | 22.52 | 23.89 | 25.02 | 25.79 | 26.21 | 26.69 | 28.37 | 30.80 | 30.10 | 29.75 | 29.19 | 28.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.101 |
| SC2 | 0 | 8 | 21.165 |
| SC3 | -18 | 7 | 17.535 |
| SC4 | -25 | 6 | 14.270 |
| SC5 | -34 | 6 | 13.070 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 520 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.