EB-330BE6-B01 C
8.82 kW
Defrost: Electric
Product code: EB-430BB4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,678 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 29.5 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.5 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BB4-B01 C | None |
|---|---|
| EB-430BB4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.73 | 3.70 | 3.69 | 3.70 | 3.68 | 3.65 | 3.61 | 3.65 | 3.87 | 4.18 | 4.08 | 4.04 | 3.99 | 3.91 |
| 5 | 4.82 | 4.86 | 4.90 | 4.94 | 4.94 | 4.92 | 4.88 | 4.90 | 5.20 | 5.61 | 5.46 | 5.40 | 5.33 | 5.22 |
| 6 | 5.83 | 5.94 | 6.06 | 6.18 | 6.26 | 6.28 | 6.25 | 6.27 | 6.65 | 7.18 | 6.98 | 6.90 | 6.79 | 6.62 |
| 7 | 6.77 | 6.92 | 7.11 | 7.28 | 7.40 | 7.46 | 7.49 | 7.56 | 8.03 | 8.71 | 8.51 | 8.44 | 8.32 | 8.14 |
| 8 | 7.63 | 7.90 | 8.16 | 8.40 | 8.55 | 8.65 | 8.69 | 8.77 | 9.31 | 10.11 | 9.88 | 9.79 | 9.65 | 9.42 |
| 9 | 8.43 | 8.82 | 9.17 | 9.50 | 9.71 | 9.85 | 9.91 | 10.01 | 10.63 | 11.53 | 11.28 | 11.17 | 11.00 | 10.72 |
| 10 | 9.19 | 9.69 | 10.16 | 10.57 | 10.85 | 11.04 | 11.11 | 11.24 | 11.94 | 12.96 | 12.68 | 12.56 | 12.37 | 12.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.680 |
| SC2 | 0 | 8 | 8.773 |
| SC3 | -18 | 7 | 7.336 |
| SC4 | -25 | 6 | 6.059 |
| SC5 | -34 | 6 | 5.858 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.