EB-445AE6-B01 C
29.07 kW
Defrost: Electric
Product code: EB-445AE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,734 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 115.1 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 146 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-445AE4-B01 C | None |
|---|---|
| EB-445AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.75 | 12.72 | 13.61 | 14.38 | 14.91 | 15.22 | 15.34 | 15.91 | 17.01 | 18.56 | 18.28 | 18.18 | 18.04 | 17.84 |
| 5 | ≈ 14.07 | 15.44 | 16.72 | 17.86 | 18.67 | 19.18 | 19.37 | 20.01 | 21.28 | 23.23 | 22.81 | 22.64 | 22.39 | 21.99 |
| 6 | ≈ 15.28 | ≈ 17.78 | 19.52 | 21.09 | 22.04 | 22.84 | 23.28 | 24.01 | 25.63 | 28.00 | 27.45 | 27.18 | 26.81 | 26.17 |
| 7 | ≈ 8.67 | ≈ 19.88 | 22.10 | 23.81 | 25.38 | 26.51 | 27.19 | 28.06 | 29.95 | 32.76 | 32.12 | 31.83 | 31.35 | 30.45 |
| 8 | not rated | ≈ 18.35 | ≈ 24.10 | 26.55 | 28.55 | 30.03 | 31.00 | 32.06 | 34.25 | 37.47 | 36.83 | 36.49 | 35.91 | 34.79 |
| 9 | ≈ 6.60 | ≈ 9.93 | ≈ 26.16 | 29.09 | 31.52 | 33.41 | 34.70 | 36.01 | 38.50 | 42.15 | 41.55 | 41.17 | 40.50 | 39.20 |
| 10 | 7.17 | ≈ 8.24 | ≈ 28.03 | 31.42 | 34.33 | 36.65 | 38.29 | 39.88 | 42.69 | 46.78 | 46.25 | 45.84 | 45.10 | 43.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 46.250 |
| SC2 | 0 | 8 | 32.062 |
| SC3 | -18 | 7 | 24.493 |
| SC4 | -25 | 6 | 19.523 |
| SC5 | -34 | 6 | 16.359 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2967 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.