EB-445AE7-B07 C
28.26 kW
Defrost: Electric
Product code: EB-445AE6-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,944 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 83.2 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 145 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-445AE6-B01 C | None |
|---|---|
| EB-445AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.93 | 11.67 | 12.35 | 12.94 | 13.33 | 13.56 | 13.66 | 14.07 | 15.03 | 16.38 | 16.11 | 16.02 | 15.86 | 15.62 |
| 5 | 13.03 | 14.29 | 15.30 | 16.10 | 16.75 | 17.16 | 17.37 | 17.84 | 19.03 | 20.74 | 20.35 | 20.20 | 19.98 | 19.62 |
| 6 | 15.09 | 16.59 | 17.99 | 19.25 | 20.17 | 20.80 | 21.02 | 21.57 | 22.97 | 25.07 | 24.61 | 24.42 | 24.12 | 23.60 |
| 7 | ≈ 16.82 | 18.67 | 20.50 | 22.16 | 23.19 | 24.09 | 24.66 | 25.33 | 27.03 | 29.53 | 29.01 | 28.78 | 28.40 | 27.69 |
| 8 | ≈ 9.78 | ≈ 20.55 | 22.31 | 24.59 | 26.22 | 27.43 | 28.24 | 29.07 | 31.04 | 33.94 | 33.42 | 33.15 | 32.71 | 31.82 |
| 9 | ≈ 5.44 | ≈ 22.23 | 24.60 | 27.07 | 29.08 | 30.63 | 31.71 | 32.76 | 35.02 | 38.32 | 37.83 | 37.54 | 37.02 | 35.99 |
| 10 | ≈ 6.78 | ≈ 13.89 | ≈ 26.48 | 29.36 | 31.80 | 33.71 | 35.10 | 36.39 | 38.94 | 42.67 | 42.23 | 41.93 | 41.35 | 40.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.228 |
| SC2 | 0 | 8 | 29.072 |
| SC3 | -18 | 7 | 22.476 |
| SC4 | -25 | 6 | 17.994 |
| SC5 | -34 | 6 | 15.420 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2967 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.