ED-DP-140AE7-B22 C
4.86 kW
Defrost: None
Product code: ED-DP-140AC4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,323 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 24.3 m² |
| Inner volume | 5.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.3 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AC4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.32 | 2.28 | 2.27 | 2.27 | 2.26 | 2.24 | 2.22 | 2.27 | 2.42 | 2.62 | 2.57 | 2.55 | 2.53 | 2.50 |
| 5 | 2.98 | 2.95 | 2.95 | 2.96 | 2.95 | 2.93 | 2.89 | 2.93 | 3.11 | 3.37 | 3.28 | 3.25 | 3.21 | 3.15 |
| 6 | 3.64 | 3.64 | 3.66 | 3.68 | 3.68 | 3.65 | 3.62 | 3.64 | 3.86 | 4.17 | 4.04 | 4.00 | 3.93 | 3.83 |
| 7 | 4.30 | 4.34 | 4.38 | 4.43 | 4.44 | 4.42 | 4.38 | 4.39 | 4.65 | 5.02 | 4.86 | 4.79 | 4.70 | 4.55 |
| 8 | 4.93 | 5.02 | 5.11 | 5.19 | 5.22 | 5.21 | 5.16 | 5.18 | 5.47 | 5.91 | 5.71 | 5.63 | 5.51 | 5.32 |
| 9 | 5.51 | 5.66 | 5.80 | 5.94 | 6.00 | 6.01 | 5.97 | 5.99 | 6.33 | 6.83 | 6.60 | 6.51 | 6.36 | 6.12 |
| 10 | 6.04 | 6.24 | 6.44 | 6.61 | 6.72 | 6.77 | 6.77 | 6.80 | 7.19 | 7.76 | 7.51 | 7.40 | 7.23 | 6.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.509 |
| SC2 | 0 | 8 | 5.177 |
| SC3 | -18 | 7 | 4.435 |
| SC4 | -25 | 6 | 3.657 |
| SC5 | -34 | 6 | 3.643 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.