ED-DP-140AC4-B22 C
5.18 kW
Defrost: None
Product code: ED-DP-140AE7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,227 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 22.9 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 64 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.6 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AE7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.15 | 2.13 | 2.12 | 2.12 | 2.11 | 2.09 | 2.07 | 2.11 | 2.25 | 2.43 | 2.38 | 2.36 | 2.34 | 2.31 |
| 5 | 2.74 | 2.74 | 2.75 | 2.77 | 2.76 | 2.75 | 2.71 | 2.75 | 2.91 | 3.15 | 3.06 | 3.03 | 2.99 | 2.92 |
| 6 | 3.32 | 3.36 | 3.40 | 3.44 | 3.45 | 3.43 | 3.40 | 3.42 | 3.62 | 3.92 | 3.79 | 3.75 | 3.68 | 3.57 |
| 7 | 3.88 | 3.96 | 4.04 | 4.11 | 4.14 | 4.14 | 4.11 | 4.13 | 4.37 | 4.72 | 4.56 | 4.50 | 4.41 | 4.25 |
| 8 | 4.44 | 4.57 | 4.69 | 4.79 | 4.85 | 4.86 | 4.83 | 4.86 | 5.14 | 5.55 | 5.36 | 5.29 | 5.17 | 4.98 |
| 9 | 4.94 | 5.13 | 5.31 | 5.47 | 5.55 | 5.58 | 5.56 | 5.60 | 5.92 | 6.39 | 6.19 | 6.10 | 5.96 | 5.73 |
| 10 | 5.41 | 5.66 | 5.90 | 6.10 | 6.24 | 6.30 | 6.30 | 6.34 | 6.71 | 7.25 | 7.03 | 6.93 | 6.77 | 6.50 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.028 |
| SC2 | 0 | 8 | 4.855 |
| SC3 | -18 | 7 | 4.128 |
| SC4 | -25 | 6 | 3.395 |
| SC5 | -34 | 6 | 3.331 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.