ED-DP-145AC7-B24 C
5.81 kW
Defrost: None
Product code: ED-DP-140AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,035 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 36.5 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.64 | 2.65 | 2.68 | 2.71 | 2.71 | 2.70 | 2.68 | 2.74 | 2.92 | 3.17 | 3.09 | 3.07 | 3.04 | 2.99 |
| 5 | 3.27 | 3.33 | 3.38 | 3.44 | 3.46 | 3.45 | 3.42 | 3.47 | 3.69 | 4.00 | 3.88 | 3.83 | 3.77 | 3.66 |
| 6 | 3.88 | 3.99 | 4.09 | 4.18 | 4.22 | 4.22 | 4.19 | 4.23 | 4.48 | 4.86 | 4.69 | 4.63 | 4.53 | 4.36 |
| 7 | 4.49 | 4.65 | 4.79 | 4.91 | 4.98 | 5.00 | 4.97 | 5.01 | 5.31 | 5.73 | 5.54 | 5.45 | 5.32 | 5.11 |
| 8 | 5.03 | 5.26 | 5.47 | 5.65 | 5.75 | 5.79 | 5.77 | 5.81 | 6.14 | 6.63 | 6.40 | 6.30 | 6.15 | 5.88 |
| 9 | 5.52 | 5.82 | 6.10 | 6.33 | 6.48 | 6.56 | 6.56 | 6.60 | 6.97 | 7.52 | 7.28 | 7.16 | 6.98 | 6.66 |
| 10 | 5.97 | 6.35 | 6.69 | 6.99 | 7.16 | 7.26 | 7.29 | 7.36 | 7.79 | 8.41 | 8.16 | 8.03 | 7.82 | 7.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.158 |
| SC2 | 0 | 8 | 5.805 |
| SC3 | -18 | 7 | 4.945 |
| SC4 | -25 | 6 | 4.087 |
| SC5 | -34 | 6 | 3.911 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.