ED-DP-445AC7-B24 C
23.27 kW
Defrost: None
Product code: ED-DP-345AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,521 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 146.1 m² |
| Inner volume | 31.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 190 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 570 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø42 |
| ED-DP-345AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.23 | 11.60 | 11.94 | 12.23 | 12.38 | 12.41 | 12.34 | 12.60 | 13.41 | 14.56 | 14.20 | 14.08 | 13.90 | 13.65 |
| 5 | 13.81 | 14.45 | 15.03 | 15.52 | 15.77 | 15.89 | 15.85 | 16.09 | 17.08 | 18.54 | 18.00 | 17.79 | 17.48 | 16.97 |
| 6 | 16.08 | 17.02 | 17.88 | 18.63 | 19.11 | 19.38 | 19.38 | 19.62 | 20.82 | 22.59 | 21.93 | 21.65 | 21.23 | 20.52 |
| 7 | 18.06 | 19.33 | 20.50 | 21.37 | 22.07 | 22.48 | 22.64 | 22.97 | 24.39 | 26.47 | 25.79 | 25.48 | 24.99 | 24.17 |
| 8 | ≈ 19.85 | 21.48 | 22.80 | 24.11 | 25.04 | 25.61 | 25.88 | 26.26 | 27.89 | 30.25 | 29.50 | 29.14 | 28.57 | 27.58 |
| 9 | ≈ 21.46 | 23.27 | 25.10 | 26.73 | 27.93 | 28.69 | 29.09 | 29.56 | 31.39 | 34.06 | 33.24 | 32.83 | 32.18 | 31.03 |
| 10 | ≈ 21.69 | ≈ 25.06 | 27.25 | 29.24 | 30.71 | 31.72 | 32.27 | 32.84 | 34.90 | 37.87 | 37.00 | 36.55 | 35.83 | 34.53 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.996 |
| SC2 | 0 | 8 | 26.264 |
| SC3 | -18 | 7 | 21.685 |
| SC4 | -25 | 6 | 17.877 |
| SC5 | -34 | 6 | 16.299 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø42 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.