ED-DR-445BA4-A27 C
13.33 kW
Defrost: None
Product code: ED-DR-345AA5-A27 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,432 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 64.1 m² |
| Inner volume | 11.4 dm³ |
| Fin spacing | 5.0 mm |
| Fin material | Aluminium |
| Net weight | 150 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 1,440 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.8 dB(A) |
| Energy class | E |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| ED-DR-345AA5-A27 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.26 | 6.19 | 6.13 | 6.08 | 6.01 | 5.94 | 5.85 | 5.82 | 6.14 | 6.61 | 6.41 | 6.34 | 6.24 | 6.10 |
| 5 | 8.17 | 8.23 | 8.27 | 8.27 | 8.22 | 8.14 | 8.03 | 7.97 | 8.42 | 9.05 | 8.76 | 8.66 | 8.50 | 8.27 |
| 6 | 9.84 | 10.06 | 10.27 | 10.47 | 10.57 | 10.56 | 10.47 | 10.41 | 10.99 | 11.83 | 11.44 | 11.30 | 11.09 | 10.77 |
| 7 | 11.31 | 11.70 | 12.04 | 12.35 | 12.53 | 12.63 | 12.66 | 12.71 | 13.48 | 14.59 | 14.25 | 14.11 | 13.92 | 13.55 |
| 8 | 12.67 | 13.26 | 13.78 | 14.22 | 14.50 | 14.67 | 14.74 | 14.82 | 15.72 | 17.02 | 16.63 | 16.47 | 16.24 | 15.87 |
| 9 | 13.94 | 14.74 | 15.45 | 16.06 | 16.47 | 16.71 | 16.85 | 16.96 | 18.00 | 19.51 | 19.07 | 18.89 | 18.63 | 18.20 |
| 10 | 15.10 | 16.13 | 17.06 | 17.86 | 18.41 | 18.76 | 18.97 | 19.13 | 20.31 | 22.03 | 21.56 | 21.36 | 21.07 | 20.58 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.73 | 5.64 | 5.57 | 5.54 | 5.48 | 5.42 | 5.36 | 5.35 | 5.65 | 6.09 | 5.92 | 5.86 | 5.77 | 5.65 |
| 5 | 7.47 | 7.47 | 7.47 | 7.47 | 7.43 | 7.35 | 7.25 | 7.22 | 7.63 | 8.22 | 7.97 | 7.88 | 7.76 | 7.56 |
| 6 | 9.12 | 9.27 | 9.39 | 9.49 | 9.50 | 9.45 | 9.36 | 9.32 | 9.85 | 10.60 | 10.27 | 10.14 | 9.97 | 9.70 |
| 7 | 10.52 | 10.80 | 11.07 | 11.31 | 11.45 | 11.52 | 11.54 | 11.59 | 12.25 | 13.21 | 12.80 | 12.64 | 12.41 | 12.06 |
| 8 | 11.82 | 12.27 | 12.67 | 13.03 | 13.24 | 13.37 | 13.42 | 13.48 | 14.30 | 15.49 | 15.13 | 14.99 | 14.78 | 14.44 |
| 9 | 13.04 | 13.67 | 14.23 | 14.72 | 15.04 | 15.22 | 15.32 | 15.41 | 16.35 | 17.72 | 17.31 | 17.15 | 16.90 | 16.51 |
| 10 | 14.17 | 15.00 | 15.74 | 16.38 | 16.82 | 17.08 | 17.23 | 17.36 | 18.42 | 19.98 | 19.53 | 19.35 | 19.08 | 18.63 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 21.555 | 19.531 |
| SC2 | 0 | 8 | 14.818 | 13.484 |
| SC3 | -18 | 7 | 12.435 | 11.376 |
| SC4 | -25 | 6 | 10.274 | 9.391 |
| SC5 | -34 | 6 | 9.902 | 9.164 |
| A | 3708 mm |
|---|---|
| B | 1215 mm |
| C | 290 mm |
| F | 1165 mm |
| G | 360 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 3395 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 3708 mm |
|---|---|
| Width | 1215 mm |
| Height | 360 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.