ED-DR-345AA5-A27 C
14.82 kW
Defrost: None
Product code: ED-DR-445BA4-A27 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 25,633 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 106.9 m² |
| Inner volume | 18.2 dm³ |
| Fin spacing | 4.0 mm |
| Fin material | Aluminium |
| Net weight | 205 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 1,920 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.5 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| ED-DR-445BA4-A27 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 8.04 | 7.99 | 7.96 | 7.91 | 7.81 |
| 5 | 2.28 | ≈ 2.23 | ≈ 4.93 | ≈ 6.62 | 7.25 | 7.77 | 8.19 | 8.55 | 9.18 | 10.11 | 10.11 | 10.09 | 10.05 | 9.97 |
| 6 | 2.68 | 2.62 | 2.62 | ≈ 7.57 | 8.40 | 9.12 | 9.71 | 10.21 | 11.00 | 12.16 | 12.22 | 12.22 | 12.20 | 12.13 |
| 7 | 3.07 | 3.01 | ≈ 2.99 | ≈ 4.90 | ≈ 9.45 | 10.37 | 11.14 | 11.81 | 12.75 | 14.16 | 14.30 | 14.33 | 14.34 | 14.30 |
| 8 | 3.45 | 3.40 | 3.38 | ≈ 3.77 | ≈ 10.41 | 11.52 | 12.49 | 13.33 | 14.44 | 16.09 | 16.34 | 16.41 | 16.46 | 16.47 |
| 9 | 3.82 | 3.77 | 3.77 | ≈ 3.78 | ≈ 7.01 | ≈ 12.58 | 13.76 | 14.78 | 16.05 | 17.95 | 18.33 | 18.43 | 18.54 | 18.61 |
| 10 | 4.18 | 4.14 | 4.14 | 4.17 | ≈ 4.66 | ≈ 13.56 | 14.94 | 16.15 | 17.58 | 19.73 | 20.26 | 20.41 | 20.58 | 20.73 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 7.45 | 7.40 | 7.37 | 7.32 | 7.22 |
| 5 | ≈ 2.07 | ≈ 2.39 | ≈ 5.65 | 6.30 | 6.84 | 7.29 | 7.63 | 7.93 | 8.52 | 9.37 | 9.34 | 9.31 | 9.27 | 9.18 |
| 6 | 2.42 | ≈ 2.37 | 3.96 | ≈ 7.23 | 7.96 | 8.57 | 9.07 | 9.49 | 10.21 | 11.26 | 11.27 | 11.26 | 11.23 | 11.14 |
| 7 | 2.77 | 2.72 | ≈ 2.71 | ≈ 8.09 | 8.99 | 9.78 | 10.44 | 10.99 | 11.85 | 13.12 | 13.19 | 13.20 | 13.18 | 13.11 |
| 8 | 3.12 | 3.06 | ≈ 3.05 | ≈ 4.60 | ≈ 9.93 | 10.91 | 11.73 | 12.44 | 13.44 | 14.93 | 15.09 | 15.12 | 15.13 | 15.08 |
| 9 | 3.45 | 3.40 | 3.39 | ≈ 3.40 | ≈ 10.79 | 11.95 | 12.96 | 13.82 | 14.97 | 16.68 | not rated | 17.00 | 17.05 | 17.05 |
| 10 | 3.78 | 3.73 | 3.72 | ≈ 3.75 | ≈ 7.26 | ≈ 12.91 | 14.10 | 15.14 | 16.43 | 18.37 | 18.75 | 18.84 | 18.94 | 18.99 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 20.255 | 18.746 |
| SC2 | 0 | 8 | 13.330 | 12.439 |
| SC3 | -18 | 7 | 8.858 | 8.455 |
| SC4 | -25 | 6 | 2.622 | 3.955 |
| SC5 | -34 | 6 | 2.670 | 2.414 |
| A | 4828 mm |
|---|---|
| B | 1215 mm |
| C | 290 mm |
| F | 1165 mm |
| G | 360 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 4515 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 4828 mm |
|---|---|
| Width | 1215 mm |
| Height | 360 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.