ED-DR-363AA5-A29 C
40.16 kW
Defrost: None
Product code: ED-DR-463BA4-A29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 71,440 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 320.7 m² |
| Inner volume | 55.5 dm³ |
| Fin spacing | 4.0 mm |
| Fin material | Aluminium |
| Net weight | 442 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 7,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| ED-DR-463BA4-A29 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 21.14 | ≈ 23.15 | ≈ 22.98 | ≈ 22.89 | ≈ 22.73 | ≈ 22.44 |
| 5 | ≈ 6.54 | not rated | ≈ 17.39 | ≈ 19.39 | ≈ 21.16 | ≈ 22.62 | ≈ 23.78 | ≈ 24.71 | ≈ 26.52 | ≈ 29.16 | ≈ 29.09 | ≈ 29.03 | ≈ 28.89 | ≈ 28.60 |
| 6 | ≈ 7.68 | ≈ 7.51 | 10.57 | ≈ 22.23 | ≈ 24.58 | ≈ 26.58 | ≈ 28.23 | ≈ 29.56 | ≈ 31.81 | ≈ 35.11 | ≈ 35.22 | ≈ 35.20 | ≈ 35.12 | ≈ 34.86 |
| 7 | ≈ 8.80 | ≈ 8.62 | ≈ 8.56 | ≈ 21.65 | ≈ 27.71 | ≈ 30.28 | ≈ 32.46 | ≈ 34.25 | ≈ 36.95 | ≈ 40.95 | ≈ 41.30 | ≈ 41.35 | ≈ 41.35 | ≈ 41.18 |
| 8 | ≈ 9.89 | ≈ 9.72 | ≈ 9.67 | ≈ 19.81 | ≈ 30.55 | ≈ 33.71 | ≈ 36.45 | 38.74 | ≈ 41.91 | ≈ 46.62 | ≈ 47.27 | ≈ 47.41 | ≈ 47.53 | ≈ 47.50 |
| 9 | ≈ 10.95 | ≈ 10.80 | ≈ 10.76 | ≈ 10.82 | ≈ 29.95 | ≈ 36.87 | ≈ 40.19 | ≈ 43.01 | ≈ 46.65 | ≈ 52.09 | ≈ 53.09 | ≈ 53.35 | ≈ 53.62 | ≈ 53.76 |
| 10 | ≈ 12.00 | ≈ 11.86 | ≈ 11.84 | ≈ 11.92 | ≈ 14.47 | ≈ 39.78 | ≈ 43.69 | ≈ 47.06 | ≈ 51.17 | ≈ 57.33 | 58.74 | ≈ 59.13 | ≈ 59.57 | ≈ 59.95 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | ≈ 23.36 | ≈ 23.19 | ≈ 23.10 | ≈ 22.94 | ≈ 22.65 |
| 5 | ≈ 6.62 | not rated | ≈ 16.64 | ≈ 19.50 | ≈ 21.30 | ≈ 22.79 | ≈ 23.97 | ≈ 24.93 | ≈ 26.75 | ≈ 29.43 | ≈ 29.37 | ≈ 29.30 | ≈ 29.17 | ≈ 28.88 |
| 6 | ≈ 7.77 | ≈ 7.59 | 8.82 | ≈ 22.35 | ≈ 24.73 | ≈ 26.77 | ≈ 28.45 | ≈ 29.82 | ≈ 32.09 | ≈ 35.43 | ≈ 35.56 | ≈ 35.54 | ≈ 35.46 | ≈ 35.21 |
| 7 | ≈ 8.90 | ≈ 8.73 | ≈ 8.66 | ≈ 20.38 | ≈ 27.87 | ≈ 30.48 | ≈ 32.70 | ≈ 34.53 | ≈ 37.27 | ≈ 41.32 | ≈ 41.68 | ≈ 41.74 | ≈ 41.75 | ≈ 41.59 |
| 8 | ≈ 10.00 | ≈ 9.84 | ≈ 9.79 | ≈ 9.90 | ≈ 30.72 | ≈ 33.92 | ≈ 36.71 | 39.05 | ≈ 42.26 | ≈ 47.02 | ≈ 47.70 | ≈ 47.86 | ≈ 47.99 | ≈ 47.97 |
| 9 | ≈ 11.08 | ≈ 10.93 | ≈ 10.90 | ≈ 10.95 | ≈ 28.66 | ≈ 37.10 | ≈ 40.47 | ≈ 43.34 | ≈ 47.03 | ≈ 52.53 | ≈ 53.57 | ≈ 53.85 | ≈ 54.13 | ≈ 54.30 |
| 10 | ≈ 12.14 | ≈ 12.00 | ≈ 11.99 | ≈ 12.07 | ≈ 12.20 | ≈ 40.01 | ≈ 43.98 | ≈ 47.41 | ≈ 51.57 | ≈ 57.80 | 59.26 | ≈ 59.67 | ≈ 60.14 | ≈ 60.54 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 58.740 | 59.260 |
| SC2 | 0 | 8 | 38.735 | 39.045 |
| SC3 | -18 | 7 | 25.984 | 26.123 |
| SC4 | -25 | 6 | 10.574 | 8.821 |
| SC5 | -34 | 6 | 7.642 | 7.731 |
| A | 4848 mm |
|---|---|
| B | 1730 mm |
| C | 788 mm |
| F | 1530 mm |
| G | 805 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 4515 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 4848 mm |
|---|---|
| Width | 1730 mm |
| Height | 805 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.