ED-DR-363AA5-A29 C
40.16 kW
Defrost: None
Product code: ED-DR-563AA5-A29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 89,722 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 323.0 m² |
| Inner volume | 67.7 dm³ |
| Fin spacing | 5.0 mm |
| Fin material | Aluminium |
| Net weight | 534 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-DR-563AA5-A29 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | ≈ 27.89 | ≈ 28.47 | ≈ 28.59 | ≈ 28.65 | ≈ 28.56 | ≈ 28.47 | ≈ 30.11 | ≈ 32.48 | ≈ 31.58 | ≈ 31.23 | ≈ 30.74 | ≈ 29.98 |
| 5 | ≈ 32.21 | ≈ 33.90 | ≈ 35.42 | ≈ 36.75 | ≈ 37.65 | ≈ 38.23 | ≈ 38.47 | ≈ 38.56 | ≈ 40.86 | ≈ 44.16 | ≈ 43.02 | ≈ 42.57 | ≈ 41.91 | ≈ 40.87 |
| 6 | ≈ 37.21 | ≈ 39.73 | 42.01 | ≈ 44.01 | ≈ 45.42 | ≈ 46.38 | ≈ 47.01 | ≈ 47.50 | ≈ 50.48 | ≈ 54.84 | ≈ 53.82 | ≈ 53.41 | ≈ 52.79 | ≈ 51.77 |
| 7 | ≈ 41.71 | ≈ 45.14 | ≈ 48.28 | ≈ 51.06 | ≈ 53.08 | ≈ 54.52 | ≈ 55.49 | ≈ 56.22 | ≈ 59.81 | ≈ 65.05 | ≈ 63.94 | ≈ 63.47 | ≈ 62.76 | ≈ 61.58 |
| 8 | ≈ 45.72 | ≈ 50.10 | ≈ 54.18 | ≈ 57.82 | ≈ 60.57 | ≈ 62.57 | ≈ 63.97 | 65.00 | ≈ 69.22 | ≈ 75.39 | ≈ 74.23 | ≈ 73.73 | ≈ 72.95 | ≈ 71.62 |
| 9 | ≈ 45.81 | ≈ 54.62 | ≈ 59.67 | ≈ 64.26 | ≈ 67.81 | ≈ 70.46 | ≈ 72.38 | ≈ 73.78 | ≈ 78.65 | ≈ 85.78 | ≈ 84.63 | ≈ 84.10 | ≈ 83.28 | ≈ 81.83 |
| 10 | ≈ 26.03 | ≈ 58.71 | ≈ 64.79 | ≈ 70.36 | ≈ 74.78 | ≈ 78.17 | ≈ 80.66 | ≈ 82.51 | ≈ 88.05 | ≈ 96.18 | 95.08 | ≈ 94.55 | ≈ 93.70 | ≈ 92.16 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | ≈ 28.19 | ≈ 28.64 | ≈ 28.93 | ≈ 28.99 | ≈ 28.90 | ≈ 28.84 | ≈ 30.47 | ≈ 32.87 | ≈ 31.95 | ≈ 31.60 | ≈ 31.09 | ≈ 30.32 |
| 5 | ≈ 32.45 | ≈ 34.18 | ≈ 35.74 | ≈ 37.10 | ≈ 38.02 | ≈ 38.62 | ≈ 38.97 | ≈ 39.07 | ≈ 41.39 | ≈ 44.74 | ≈ 43.58 | ≈ 43.13 | ≈ 42.46 | ≈ 41.41 |
| 6 | ≈ 37.46 | ≈ 40.04 | 42.38 | ≈ 44.43 | ≈ 45.88 | ≈ 46.86 | ≈ 47.51 | ≈ 48.01 | ≈ 51.03 | ≈ 55.43 | ≈ 54.41 | ≈ 53.99 | ≈ 53.36 | ≈ 52.33 |
| 7 | ≈ 41.97 | ≈ 45.47 | ≈ 48.69 | ≈ 51.53 | ≈ 53.61 | ≈ 55.09 | ≈ 56.08 | ≈ 56.84 | ≈ 60.47 | ≈ 65.77 | ≈ 64.65 | ≈ 64.18 | ≈ 63.46 | ≈ 62.26 |
| 8 | ≈ 46.00 | ≈ 50.45 | ≈ 54.62 | ≈ 58.34 | ≈ 61.18 | ≈ 63.21 | ≈ 64.65 | 65.71 | ≈ 69.99 | ≈ 76.23 | ≈ 75.06 | ≈ 74.56 | ≈ 73.78 | ≈ 72.43 |
| 9 | ≈ 44.30 | ≈ 54.99 | ≈ 60.14 | ≈ 64.82 | ≈ 68.46 | ≈ 71.18 | ≈ 73.14 | ≈ 74.59 | ≈ 79.52 | ≈ 86.75 | ≈ 85.59 | ≈ 85.06 | ≈ 84.23 | ≈ 82.77 |
| 10 | ≈ 21.49 | ≈ 59.09 | ≈ 65.27 | ≈ 70.96 | ≈ 75.48 | ≈ 78.95 | ≈ 81.51 | ≈ 83.42 | ≈ 89.03 | ≈ 97.26 | 96.16 | ≈ 95.64 | ≈ 94.78 | ≈ 93.24 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 95.077 | 96.162 |
| SC2 | 0 | 8 | 64.999 | 65.712 |
| SC3 | -18 | 7 | 51.949 | 52.447 |
| SC4 | -25 | 6 | 42.013 | 42.383 |
| SC5 | -34 | 6 | 37.788 | 38.052 |
| A | 5968 mm |
|---|---|
| B | 1730 mm |
| C | 788 mm |
| F | 1530 mm |
| G | 805 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 5635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 5968 mm |
|---|---|
| Width | 1730 mm |
| Height | 805 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.