ED-130AC4-C21 C
2.52 kW
Defrost: Electric
Product code: ED-130AE7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,281 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 9.3 m² |
| Inner volume | 2.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.2 dB(A) |
| Energy class | A |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-130AE7-C21 C | None |
|---|---|
| ED-130AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.13 | 1.12 | 1.12 | 1.12 | 1.11 | 1.10 | 1.09 | 1.10 | 1.17 | 1.27 | 1.24 | 1.23 | 1.21 | 1.20 |
| 5 | 1.45 | 1.45 | 1.46 | 1.47 | 1.46 | 1.46 | 1.44 | 1.45 | 1.54 | 1.66 | 1.61 | 1.60 | 1.57 | 1.54 |
| 6 | 1.76 | 1.78 | 1.80 | 1.83 | 1.83 | 1.83 | 1.82 | 1.82 | 1.93 | 2.09 | 2.02 | 2.00 | 1.96 | 1.90 |
| 7 | 2.06 | 2.11 | 2.15 | 2.19 | 2.21 | 2.22 | 2.20 | 2.21 | 2.34 | 2.53 | 2.45 | 2.42 | 2.37 | 2.29 |
| 8 | 2.35 | 2.42 | 2.49 | 2.55 | 2.59 | 2.60 | 2.60 | 2.61 | 2.77 | 2.99 | 2.90 | 2.86 | 2.80 | 2.71 |
| 9 | 2.60 | 2.70 | 2.80 | 2.89 | 2.95 | 2.98 | 2.99 | 3.02 | 3.19 | 3.45 | 3.36 | 3.31 | 3.25 | 3.13 |
| 10 | 2.84 | 2.97 | 3.10 | 3.21 | 3.28 | 3.33 | 3.35 | 3.39 | 3.59 | 3.89 | 3.80 | 3.76 | 3.69 | 3.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.799 |
| SC2 | 0 | 8 | 2.611 |
| SC3 | -18 | 7 | 2.202 |
| SC4 | -25 | 6 | 1.804 |
| SC5 | -34 | 6 | 1.767 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.