ED-140AC7-C21 C
4.78 kW
Defrost: Electric
Product code: ED-135AC4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,476 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 18.3 m² |
| Inner volume | 3.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-135AC4-C21 C | None |
|---|---|
| ED-135AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.92 | 1.98 | 2.03 | 2.07 | 2.08 | 2.08 | 2.06 | 2.09 | 2.22 | 2.40 | 2.35 | 2.33 | 2.30 | 2.25 |
| 5 | 2.42 | 2.53 | 2.63 | 2.71 | 2.76 | 2.77 | 2.76 | 2.80 | 2.97 | 3.21 | 3.12 | 3.09 | 3.05 | 2.98 |
| 6 | 2.84 | 3.01 | 3.16 | 3.30 | 3.37 | 3.42 | 3.45 | 3.50 | 3.72 | 4.05 | 3.95 | 3.91 | 3.85 | 3.74 |
| 7 | 3.20 | 3.44 | 3.62 | 3.81 | 3.94 | 4.02 | 4.07 | 4.13 | 4.40 | 4.78 | 4.67 | 4.63 | 4.56 | 4.45 |
| 8 | ≈ 3.53 | 3.80 | 4.08 | 4.32 | 4.50 | 4.62 | 4.69 | 4.77 | 5.07 | 5.52 | 5.40 | 5.34 | 5.26 | 5.12 |
| 9 | ≈ 3.71 | 4.16 | 4.50 | 4.81 | 5.04 | 5.21 | 5.30 | 5.41 | 5.75 | 6.26 | 6.13 | 6.07 | 5.98 | 5.81 |
| 10 | ≈ 3.82 | ≈ 4.48 | 4.90 | 5.28 | 5.57 | 5.78 | 5.92 | 6.04 | 6.43 | 7.00 | 6.87 | 6.80 | 6.70 | 6.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.871 |
| SC2 | 0 | 8 | 4.769 |
| SC3 | -18 | 7 | 3.867 |
| SC4 | -25 | 6 | 3.163 |
| SC5 | -34 | 6 | 2.877 |
| A | 948 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 948 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.