ED-230AE7-C21 C
5.43 kW
Defrost: None
Product code: ED-135AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,190 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 27.4 m² |
| Inner volume | 6.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø28 |
| ED-135AE4-C21 C | None |
|---|---|
| ED-135AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.44 | 2.41 | 2.41 | 2.41 | 2.40 | 2.38 | 2.36 | 2.41 | 2.56 | 2.78 | 2.72 | 2.71 | 2.68 | 2.65 |
| 5 | 3.11 | 3.11 | 3.11 | 3.13 | 3.12 | 3.10 | 3.06 | 3.10 | 3.29 | 3.56 | 3.46 | 3.43 | 3.38 | 3.32 |
| 6 | 3.77 | 3.80 | 3.84 | 3.88 | 3.88 | 3.86 | 3.81 | 3.84 | 4.07 | 4.40 | 4.26 | 4.20 | 4.13 | 4.01 |
| 7 | 4.43 | 4.51 | 4.57 | 4.64 | 4.66 | 4.65 | 4.60 | 4.62 | 4.89 | 5.28 | 5.09 | 5.02 | 4.92 | 4.74 |
| 8 | 5.05 | 5.18 | 5.31 | 5.41 | 5.46 | 5.45 | 5.41 | 5.42 | 5.73 | 6.18 | 5.97 | 5.88 | 5.75 | 5.53 |
| 9 | 5.61 | 5.80 | 5.98 | 6.15 | 6.24 | 6.27 | 6.23 | 6.25 | 6.60 | 7.12 | 6.88 | 6.77 | 6.61 | 6.34 |
| 10 | 6.11 | 6.38 | 6.62 | 6.83 | 6.95 | 7.00 | 7.00 | 7.05 | 7.46 | 8.06 | 7.80 | 7.67 | 7.49 | 7.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.795 |
| SC2 | 0 | 8 | 5.423 |
| SC3 | -18 | 7 | 4.652 |
| SC4 | -25 | 6 | 3.839 |
| SC5 | -34 | 6 | 3.784 |
| A | 948 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.