ED-240AE7-C21 C
12.75 kW
Defrost: None
Product code: ED-150AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,085 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 42.6 m² |
| Inner volume | 14.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 87 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 680 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.6 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-150AE7-C21 C | None |
|---|---|
| ED-150AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.45 | 5.29 | 5.18 | 5.12 | 5.05 | 4.97 | 4.89 | 4.92 | 5.21 | 5.62 | 5.46 | 5.41 | 5.33 | 5.21 |
| 5 | 7.20 | 7.06 | 6.97 | 6.91 | 6.83 | 6.73 | 6.61 | 6.61 | 6.99 | 7.54 | 7.30 | 7.22 | 7.11 | 6.95 |
| 6 | 8.97 | 8.90 | 8.86 | 8.84 | 8.77 | 8.66 | 8.52 | 8.50 | 8.98 | 9.66 | 9.33 | 9.21 | 9.04 | 8.80 |
| 7 | 10.76 | 10.74 | 10.79 | 10.84 | 10.81 | 10.72 | 10.58 | 10.54 | 11.13 | 11.97 | 11.54 | 11.38 | 11.15 | 10.79 |
| 8 | 12.45 | 12.59 | 12.75 | 12.89 | 12.90 | 12.85 | 12.72 | 12.68 | 13.39 | 14.42 | 13.91 | 13.70 | 13.40 | 12.92 |
| 9 | 14.00 | 14.29 | 14.59 | 14.89 | 15.02 | 15.01 | 14.91 | 14.89 | 15.73 | 16.95 | 16.38 | 16.14 | 15.78 | 15.19 |
| 10 | 15.39 | 15.83 | 16.26 | 16.66 | 16.89 | 17.02 | 17.02 | 17.11 | 18.11 | 19.53 | 18.90 | 18.63 | 18.22 | 17.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.901 |
| SC2 | 0 | 8 | 12.679 |
| SC3 | -18 | 7 | 10.840 |
| SC4 | -25 | 6 | 8.862 |
| SC5 | -34 | 6 | 8.970 |
| A | 1368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 1035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.