ED-240AE7-C21 C
12.75 kW
Defrost: None
Product code: ED-530AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,846 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 63.0 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 107 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-530AC4-C25 C | None |
|---|---|
| ED-530AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.48 | 5.55 | 5.62 | 5.68 | 5.69 | 5.66 | 5.61 | 5.71 | 6.07 | 6.57 | 6.41 | 6.36 | 6.29 | 6.19 |
| 5 | 6.92 | 7.11 | 7.28 | 7.41 | 7.47 | 7.47 | 7.41 | 7.50 | 7.96 | 8.61 | 8.36 | 8.27 | 8.14 | 7.95 |
| 6 | 8.23 | 8.55 | 8.86 | 9.12 | 9.29 | 9.36 | 9.32 | 9.40 | 9.95 | 10.77 | 10.45 | 10.32 | 10.13 | 9.83 |
| 7 | 9.35 | 9.83 | 10.27 | 10.60 | 10.85 | 10.99 | 11.04 | 11.17 | 11.86 | 12.87 | 12.55 | 12.41 | 12.21 | 11.84 |
| 8 | 10.39 | 10.97 | 11.56 | 12.07 | 12.42 | 12.62 | 12.71 | 12.87 | 13.66 | 14.82 | 14.46 | 14.30 | 14.05 | 13.62 |
| 9 | 11.33 | 12.09 | 12.84 | 13.50 | 13.96 | 14.25 | 14.39 | 14.58 | 15.49 | 16.80 | 16.40 | 16.21 | 15.93 | 15.41 |
| 10 | 12.13 | 13.13 | 14.06 | 14.89 | 15.47 | 15.86 | 16.06 | 16.30 | 17.32 | 18.79 | 18.36 | 18.15 | 17.83 | 17.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.361 |
| SC2 | 0 | 8 | 12.870 |
| SC3 | -18 | 7 | 10.711 |
| SC4 | -25 | 6 | 8.855 |
| SC5 | -34 | 6 | 8.305 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.