ED-430AE4-C21 C
13.32 kW
Defrost: None
Product code: ED-630AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,424 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 47.2 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.4 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-630AC7-C21 C | None |
|---|---|
| ED-630AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.38 | 5.47 | 5.55 | 5.62 | 5.63 | 5.60 | 5.55 | 5.59 | 5.93 | 6.40 | 6.22 | 6.16 | 6.07 | 5.92 |
| 5 | 6.83 | 7.06 | 7.27 | 7.42 | 7.51 | 7.54 | 7.51 | 7.56 | 8.02 | 8.67 | 8.42 | 8.32 | 8.19 | 7.99 |
| 6 | 8.13 | 8.51 | 8.87 | 9.19 | 9.40 | 9.53 | 9.56 | 9.61 | 10.20 | 11.05 | 10.75 | 10.64 | 10.46 | 10.18 |
| 7 | 9.23 | 9.78 | 10.29 | 10.67 | 10.99 | 11.20 | 11.32 | 11.48 | 12.20 | 13.27 | 12.99 | 12.88 | 12.70 | 12.41 |
| 8 | 10.24 | 10.90 | 11.56 | 12.16 | 12.59 | 12.89 | 13.07 | 13.27 | 14.12 | 15.36 | 15.06 | 14.92 | 14.72 | 14.37 |
| 9 | ≈ 11.15 | 11.99 | 12.83 | 13.59 | 14.15 | 14.56 | 14.81 | 15.07 | 16.04 | 17.46 | 17.14 | 16.99 | 16.76 | 16.36 |
| 10 | ≈ 11.90 | 13.00 | 14.03 | 14.96 | 15.68 | 16.20 | 16.54 | 16.87 | 17.97 | 19.57 | 19.24 | 19.08 | 18.83 | 18.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.242 |
| SC2 | 0 | 8 | 13.274 |
| SC3 | -18 | 7 | 10.815 |
| SC4 | -25 | 6 | 8.868 |
| SC5 | -34 | 6 | 8.222 |
| A | 3348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 3035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.