ED-630AC7-C21 C
13.27 kW
Defrost: None
Product code: ED-430AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,751 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 76.1 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 106 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | A |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-430AE4-C21 C | None |
|---|---|
| ED-430AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.65 | 5.86 | 6.06 | 6.22 | 6.31 | 6.35 | 6.32 | 6.45 | 6.86 | 7.45 | 7.27 | 7.20 | 7.11 | 6.97 |
| 5 | 6.91 | 7.27 | 7.59 | 7.86 | 8.01 | 8.09 | 8.09 | 8.21 | 8.72 | 9.47 | 9.20 | 9.10 | 8.94 | 8.68 |
| 6 | 8.02 | 8.53 | 8.99 | 9.40 | 9.67 | 9.79 | 9.85 | 9.99 | 10.60 | 11.51 | 11.19 | 11.05 | 10.84 | 10.48 |
| 7 | 8.98 | 9.66 | 10.29 | 10.75 | 11.14 | 11.38 | 11.48 | 11.66 | 12.38 | 13.45 | 13.11 | 12.96 | 12.72 | 12.31 |
| 8 | ≈ 9.85 | 10.71 | 11.41 | 12.11 | 12.62 | 12.94 | 13.11 | 13.32 | 14.15 | 15.36 | 14.99 | 14.81 | 14.54 | 14.04 |
| 9 | ≈ 10.63 | 11.57 | 12.53 | 13.40 | 14.05 | 14.48 | 14.72 | 14.97 | 15.91 | 17.27 | 16.88 | 16.68 | 16.36 | 15.80 |
| 10 | ≈ 9.77 | ≈ 12.44 | 13.59 | 14.63 | 15.43 | 15.98 | 16.31 | 16.62 | 17.67 | 19.19 | 18.77 | 18.56 | 18.21 | 17.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.774 |
| SC2 | 0 | 8 | 13.318 |
| SC3 | -18 | 7 | 10.927 |
| SC4 | -25 | 6 | 8.991 |
| SC5 | -34 | 6 | 8.135 |
| A | 2348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.