ED-530AE7-C25 C
13.71 kW
Defrost: None
Product code: ED-245AC7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,791 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 40.7 m² |
| Inner volume | 14.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-245AC7-C23 C | None |
|---|---|
| ED-245AC7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.61 | 5.52 | 5.46 | 5.42 | 5.36 | 5.28 | 5.20 | 5.21 | 5.51 | 5.92 | 5.74 | 5.68 | 5.59 | 5.45 |
| 5 | 7.34 | 7.34 | 7.35 | 7.36 | 7.32 | 7.25 | 7.15 | 7.14 | 7.55 | 8.13 | 7.88 | 7.78 | 7.65 | 7.46 |
| 6 | 9.07 | 9.19 | 9.31 | 9.39 | 9.41 | 9.37 | 9.28 | 9.28 | 9.81 | 10.57 | 10.22 | 10.10 | 9.91 | 9.64 |
| 7 | 10.68 | 10.97 | 11.23 | 11.46 | 11.57 | 11.59 | 11.53 | 11.54 | 12.21 | 13.18 | 12.76 | 12.61 | 12.37 | 12.00 |
| 8 | 12.06 | 12.49 | 12.89 | 13.27 | 13.51 | 13.62 | 13.70 | 13.81 | 14.66 | 15.87 | 15.42 | 15.24 | 14.97 | 14.52 |
| 9 | 13.34 | 13.95 | 14.44 | 14.95 | 15.29 | 15.52 | 15.64 | 15.79 | 16.76 | 18.19 | 17.79 | 17.63 | 17.38 | 16.96 |
| 10 | 14.53 | 15.26 | 15.99 | 16.64 | 17.09 | 17.40 | 17.58 | 17.77 | 18.88 | 20.50 | 20.08 | 19.89 | 19.61 | 19.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.076 |
| SC2 | 0 | 8 | 13.812 |
| SC3 | -18 | 7 | 11.519 |
| SC4 | -25 | 6 | 9.307 |
| SC5 | -34 | 6 | 9.111 |
| A | 1948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.