ED-335AE7-C21 C
14.11 kW
Defrost: None
Product code: ED-530AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,597 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 63.0 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 114 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.1 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-530AC4-C21 C | None |
|---|---|
| ED-530AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.91 | 6.02 | 6.12 | 6.20 | 6.22 | 6.20 | 6.14 | 6.23 | 6.62 | 7.17 | 6.99 | 6.93 | 6.85 | 6.73 |
| 5 | 7.45 | 7.71 | 7.93 | 8.12 | 8.21 | 8.22 | 8.17 | 8.26 | 8.76 | 9.48 | 9.20 | 9.10 | 8.96 | 8.74 |
| 6 | 8.77 | 9.18 | 9.55 | 9.87 | 10.04 | 10.16 | 10.20 | 10.33 | 10.98 | 11.91 | 11.57 | 11.44 | 11.24 | 10.92 |
| 7 | 9.94 | 10.52 | 10.98 | 11.44 | 11.76 | 11.94 | 12.03 | 12.18 | 12.94 | 14.05 | 13.71 | 13.58 | 13.37 | 13.03 |
| 8 | 11.00 | 11.70 | 12.40 | 13.02 | 13.45 | 13.72 | 13.86 | 14.05 | 14.92 | 16.20 | 15.83 | 15.67 | 15.43 | 15.01 |
| 9 | 11.90 | 12.86 | 13.75 | 14.54 | 15.10 | 15.48 | 15.68 | 15.92 | 16.92 | 18.38 | 17.98 | 17.79 | 17.51 | 17.03 |
| 10 | ≈ 12.77 | 13.93 | 15.02 | 16.00 | 16.72 | 17.21 | 17.50 | 17.80 | 18.92 | 20.56 | 20.14 | 19.94 | 19.63 | 19.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.142 |
| SC2 | 0 | 8 | 14.045 |
| SC3 | -18 | 7 | 11.585 |
| SC4 | -25 | 6 | 9.546 |
| SC5 | -34 | 6 | 8.865 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |