ED-245AC7-C23 C
13.81 kW
Defrost: None
Product code: ED-530AE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,614 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 59.6 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 117 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-530AE7-C25 C | None |
|---|---|
| ED-530AE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.17 | 6.13 | 6.12 | 6.13 | 6.12 | 6.07 | 6.00 | 6.11 | 6.50 | 7.04 | 6.87 | 6.81 | 6.74 | 6.63 |
| 5 | 7.81 | 7.83 | 7.88 | 7.94 | 7.95 | 7.90 | 7.82 | 7.90 | 8.38 | 9.07 | 8.80 | 8.70 | 8.56 | 8.35 |
| 6 | 9.41 | 9.52 | 9.65 | 9.78 | 9.83 | 9.81 | 9.72 | 9.79 | 10.36 | 11.21 | 10.84 | 10.69 | 10.48 | 10.13 |
| 7 | 11.00 | 11.21 | 11.41 | 11.62 | 11.73 | 11.74 | 11.66 | 11.73 | 12.41 | 13.41 | 12.96 | 12.77 | 12.48 | 12.01 |
| 8 | 12.46 | 12.82 | 13.16 | 13.48 | 13.65 | 13.69 | 13.63 | 13.71 | 14.50 | 15.66 | 15.15 | 14.92 | 14.57 | 13.99 |
| 9 | 13.82 | 14.32 | 14.81 | 15.25 | 15.52 | 15.65 | 15.62 | 15.71 | 16.62 | 17.94 | 17.37 | 17.11 | 16.70 | 16.02 |
| 10 | 15.05 | 15.72 | 16.35 | 16.92 | 17.27 | 17.43 | 17.49 | 17.65 | 18.70 | 20.22 | 19.60 | 19.30 | 18.85 | 18.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.595 |
| SC2 | 0 | 8 | 13.708 |
| SC3 | -18 | 7 | 11.679 |
| SC4 | -25 | 6 | 9.649 |
| SC5 | -34 | 6 | 9.446 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.