ED-245AC7-C23 C
13.81 kW
Defrost: Electric
Product code: ED-530AE7-C25 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,614 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 59.6 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 117 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-530AE7-C25 C | None |
|---|---|
| ED-530AE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.59 | 5.55 | 5.55 | 5.58 | 5.58 | 5.56 | 5.52 | 5.65 | 6.02 | 6.54 | 6.41 | 6.37 | 6.32 | 6.25 |
| 5 | 7.23 | 7.24 | 7.29 | 7.36 | 7.38 | 7.36 | 7.30 | 7.41 | 7.87 | 8.54 | 8.31 | 8.23 | 8.12 | 7.95 |
| 6 | 8.84 | 8.94 | 9.06 | 9.19 | 9.25 | 9.24 | 9.17 | 9.27 | 9.83 | 10.64 | 10.32 | 10.20 | 10.01 | 9.71 |
| 7 | 10.45 | 10.60 | 10.82 | 11.03 | 11.14 | 11.16 | 11.10 | 11.19 | 11.86 | 12.83 | 12.42 | 12.25 | 11.99 | 11.56 |
| 8 | 11.94 | 12.26 | 12.58 | 12.88 | 13.04 | 13.10 | 13.06 | 13.16 | 13.93 | 15.05 | 14.58 | 14.37 | 14.06 | 13.53 |
| 9 | 13.34 | 13.81 | 14.27 | 14.70 | 14.94 | 15.06 | 15.03 | 15.15 | 16.04 | 17.32 | 16.80 | 16.55 | 16.18 | 15.54 |
| 10 | 14.61 | 15.23 | 15.83 | 16.37 | 16.72 | 16.92 | 16.96 | 17.13 | 18.14 | 19.59 | 19.01 | 18.74 | 18.31 | 17.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.014 |
| SC2 | 0 | 8 | 13.158 |
| SC3 | -18 | 7 | 11.085 |
| SC4 | -25 | 6 | 9.060 |
| SC5 | -34 | 6 | 8.872 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.