ED-150AE7-C21 C
12.68 kW
Defrost: None
Product code: ED-240AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,401 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 45.8 m² |
| Inner volume | 15.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 94 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-240AE7-C21 C | None |
|---|---|
| ED-240AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.39 | 5.34 | 5.33 | 5.32 | 5.29 | 5.24 | 5.17 | 5.22 | 5.54 | 5.99 | 5.83 | 5.78 | 5.71 | 5.58 |
| 5 | 6.91 | 6.95 | 7.00 | 7.05 | 7.04 | 7.00 | 6.92 | 6.96 | 7.37 | 7.96 | 7.72 | 7.64 | 7.52 | 7.35 |
| 6 | 8.43 | 8.54 | 8.69 | 8.83 | 8.88 | 8.86 | 8.79 | 8.82 | 9.34 | 10.08 | 9.76 | 9.64 | 9.46 | 9.19 |
| 7 | 9.83 | 10.12 | 10.39 | 10.63 | 10.75 | 10.77 | 10.72 | 10.76 | 11.39 | 12.31 | 11.92 | 11.77 | 11.54 | 11.15 |
| 8 | 11.12 | 11.55 | 11.96 | 12.33 | 12.57 | 12.70 | 12.69 | 12.75 | 13.51 | 14.59 | 14.16 | 13.97 | 13.69 | 13.20 |
| 9 | 12.25 | 12.85 | 13.40 | 13.89 | 14.16 | 14.36 | 14.45 | 14.60 | 15.49 | 16.80 | 16.40 | 16.22 | 15.89 | 15.31 |
| 10 | 13.31 | 14.09 | 14.72 | 15.34 | 15.77 | 16.04 | 16.18 | 16.37 | 17.38 | 18.84 | 18.41 | 18.20 | 17.88 | 17.29 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.414 |
| SC2 | 0 | 8 | 12.754 |
| SC3 | -18 | 7 | 10.689 |
| SC4 | -25 | 6 | 8.691 |
| SC5 | -34 | 6 | 8.471 |
| A | 1548 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1548 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.