ED-430AE4-C21 C
13.32 kW
Defrost: None
Product code: ED-630AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 8,424 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 47.2 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.4 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-630AC7-C21 C | None |
|---|---|
| ED-630AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.86 | 4.93 | 4.99 | 5.06 | 5.07 | 5.06 | 5.03 | 5.09 | 5.41 | 5.85 | 5.71 | 5.65 | 5.57 | 5.45 |
| 5 | 6.34 | 6.50 | 6.68 | 6.85 | 6.93 | 6.96 | 6.94 | 7.02 | 7.45 | 8.06 | 7.85 | 7.78 | 7.67 | 7.52 |
| 6 | 7.68 | 8.05 | 8.38 | 8.67 | 8.85 | 8.95 | 8.96 | 9.06 | 9.62 | 10.43 | 10.15 | 10.05 | 9.90 | 9.66 |
| 7 | 8.85 | 9.35 | 9.82 | 10.19 | 10.49 | 10.70 | 10.82 | 10.99 | 11.69 | 12.72 | 12.47 | 12.37 | 12.22 | 11.95 |
| 8 | 9.88 | 10.57 | 11.12 | 11.68 | 12.10 | 12.39 | 12.57 | 12.78 | 13.60 | 14.81 | 14.53 | 14.41 | 14.23 | 13.91 |
| 9 | 10.83 | 11.62 | 12.41 | 13.13 | 13.67 | 14.06 | 14.31 | 14.57 | 15.52 | 16.90 | 16.61 | 16.47 | 16.26 | 15.89 |
| 10 | ≈ 11.50 | 12.65 | 13.63 | 14.52 | 15.20 | 15.70 | 16.04 | 16.37 | 17.44 | 19.00 | 18.70 | 18.55 | 18.31 | 17.89 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.699 |
| SC2 | 0 | 8 | 12.777 |
| SC3 | -18 | 7 | 10.322 |
| SC4 | -25 | 6 | 8.378 |
| SC5 | -34 | 6 | 7.768 |
| A | 3348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 3035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.