ED-240AE7-C21 C
12.75 kW
Defrost: Electric
Product code: ED-530AC4-C25 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,846 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 63.0 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 107 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-530AC4-C25 C | None |
|---|---|
| ED-530AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.97 | 5.02 | 5.08 | 5.14 | 5.17 | 5.16 | 5.13 | 5.25 | 5.59 | 6.07 | 5.96 | 5.92 | 5.87 | 5.80 |
| 5 | 6.43 | 6.59 | 6.71 | 6.85 | 6.92 | 6.93 | 6.89 | 7.00 | 7.44 | 8.07 | 7.86 | 7.79 | 7.69 | 7.54 |
| 6 | 7.78 | 8.09 | 8.37 | 8.61 | 8.75 | 8.80 | 8.77 | 8.87 | 9.42 | 10.21 | 9.92 | 9.81 | 9.65 | 9.39 |
| 7 | 8.96 | 9.40 | 9.80 | 10.16 | 10.36 | 10.50 | 10.56 | 10.71 | 11.38 | 12.36 | 12.07 | 11.93 | 11.72 | 11.37 |
| 8 | 10.02 | 10.63 | 11.11 | 11.60 | 11.93 | 12.13 | 12.23 | 12.40 | 13.17 | 14.31 | 13.97 | 13.82 | 13.60 | 13.21 |
| 9 | 11.00 | 11.71 | 12.41 | 13.04 | 13.48 | 13.76 | 13.90 | 14.11 | 14.99 | 16.27 | 15.90 | 15.73 | 15.47 | 14.99 |
| 10 | 11.83 | 12.77 | 13.65 | 14.44 | 15.00 | 15.37 | 15.57 | 15.82 | 16.81 | 18.25 | 17.85 | 17.66 | 17.36 | 16.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.854 |
| SC2 | 0 | 8 | 12.399 |
| SC3 | -18 | 7 | 10.226 |
| SC4 | -25 | 6 | 8.368 |
| SC5 | -34 | 6 | 7.855 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.