ED-340AC7-C21 C
14.85 kW
Defrost: None
Product code: ED-240AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,914 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 73.0 m² |
| Inner volume | 16.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 98 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-240AE4-C21 C | None |
|---|---|
| ED-240AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.45 | 6.50 | 6.56 | 6.61 | 6.62 | 6.58 | 6.51 | 6.65 | 7.08 | 7.68 | 7.50 | 7.44 | 7.37 | 7.25 |
| 5 | 8.09 | 8.27 | 8.43 | 8.57 | 8.62 | 8.59 | 8.50 | 8.62 | 9.15 | 9.91 | 9.61 | 9.51 | 9.36 | 9.13 |
| 6 | 9.70 | 10.03 | 10.32 | 10.57 | 10.67 | 10.68 | 10.60 | 10.70 | 11.34 | 12.27 | 11.86 | 11.70 | 11.47 | 11.10 |
| 7 | 11.13 | 11.62 | 12.07 | 12.46 | 12.70 | 12.80 | 12.76 | 12.83 | 13.59 | 14.70 | 14.21 | 14.01 | 13.71 | 13.21 |
| 8 | 12.39 | 13.07 | 13.68 | 14.14 | 14.48 | 14.65 | 14.69 | 14.85 | 15.74 | 17.05 | 16.57 | 16.36 | 16.02 | 15.40 |
| 9 | 13.55 | 14.44 | 15.14 | 15.83 | 16.27 | 16.53 | 16.61 | 16.79 | 17.81 | 19.28 | 18.75 | 18.50 | 18.13 | 17.47 |
| 10 | 14.61 | 15.62 | 16.60 | 17.46 | 18.04 | 18.39 | 18.53 | 18.75 | 19.89 | 21.53 | 20.95 | 20.67 | 20.24 | 19.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.951 |
| SC2 | 0 | 8 | 14.845 |
| SC3 | -18 | 7 | 12.569 |
| SC4 | -25 | 6 | 10.323 |
| SC5 | -34 | 6 | 9.787 |
| A | 1548 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 1548 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.