ED-163AE7-C27 C
14.82 kW
Defrost: None
Product code: ED-530AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,099 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 95.1 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-530AE4-C25 C | None |
|---|---|
| ED-530AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.82 | 6.82 | 6.86 | 6.91 | 6.92 | 6.89 | 6.81 | 6.97 | 7.42 | 8.06 | 7.87 | 7.80 | 7.71 | 7.59 |
| 5 | 8.49 | 8.57 | 8.68 | 8.79 | 8.82 | 8.79 | 8.70 | 8.82 | 9.36 | 10.15 | 9.83 | 9.72 | 9.54 | 9.27 |
| 6 | 10.10 | 10.30 | 10.50 | 10.68 | 10.76 | 10.75 | 10.64 | 10.74 | 11.38 | 12.31 | 11.89 | 11.72 | 11.47 | 11.05 |
| 7 | 11.70 | 12.02 | 12.32 | 12.59 | 12.71 | 12.73 | 12.62 | 12.71 | 13.44 | 14.52 | 14.03 | 13.82 | 13.49 | 12.96 |
| 8 | 13.15 | 13.63 | 14.08 | 14.46 | 14.68 | 14.73 | 14.62 | 14.71 | 15.56 | 16.78 | 16.22 | 15.96 | 15.57 | 14.93 |
| 9 | 14.47 | 15.11 | 15.70 | 16.22 | 16.54 | 16.67 | 16.64 | 16.71 | 17.67 | 19.05 | 18.42 | 18.13 | 17.67 | 16.93 |
| 10 | 15.69 | 16.52 | 17.28 | 17.86 | 18.28 | 18.48 | 18.50 | 18.63 | 19.71 | 21.28 | 20.64 | 20.33 | 19.81 | 18.97 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.642 |
| SC2 | 0 | 8 | 14.712 |
| SC3 | -18 | 7 | 12.641 |
| SC4 | -25 | 6 | 10.495 |
| SC5 | -34 | 6 | 10.157 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.