ED-163AE7-C27 C
14.82 kW
Defrost: None
Product code: ED-530AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,099 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 95.1 m² |
| Inner volume | 20.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-530AE4-C25 C | None |
|---|---|
| ED-530AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.21 | 6.22 | 6.27 | 6.33 | 6.36 | 6.35 | 6.30 | 6.49 | 6.93 | 7.54 | 7.40 | 7.35 | 7.30 | 7.22 |
| 5 | 7.90 | 7.97 | 8.08 | 8.19 | 8.24 | 8.23 | 8.16 | 8.31 | 8.84 | 9.60 | 9.34 | 9.24 | 9.10 | 8.88 |
| 6 | 9.53 | 9.71 | 9.89 | 10.07 | 10.16 | 10.17 | 10.09 | 10.21 | 10.83 | 11.74 | 11.37 | 11.22 | 11.00 | 10.64 |
| 7 | 11.15 | 11.44 | 11.72 | 11.96 | 12.11 | 12.14 | 12.05 | 12.17 | 12.88 | 13.93 | 13.48 | 13.29 | 13.00 | 12.51 |
| 8 | 12.64 | 13.07 | 13.49 | 13.86 | 14.07 | 14.12 | 14.05 | 14.16 | 14.98 | 16.18 | 15.66 | 15.42 | 15.06 | 14.47 |
| 9 | 14.01 | 14.60 | 15.16 | 15.65 | 15.97 | 16.10 | 16.06 | 16.16 | 17.10 | 18.44 | 17.86 | 17.58 | 17.15 | 16.46 |
| 10 | 15.26 | 16.03 | 16.75 | 17.37 | 17.72 | 17.92 | 17.95 | 18.09 | 19.16 | 20.70 | 20.08 | 19.77 | 19.28 | 18.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.080 |
| SC2 | 0 | 8 | 14.157 |
| SC3 | -18 | 7 | 12.034 |
| SC4 | -25 | 6 | 9.893 |
| SC5 | -34 | 6 | 9.579 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.