ED-530AE4-C25 C
14.71 kW
Defrost: None
Product code: ED-150AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,648 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 68.1 m² |
| Inner volume | 14.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 91 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 680 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.1 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-150AE4-C21 C | None |
|---|---|
| ED-150AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.37 | 6.24 | 6.17 | 6.14 | 6.09 | 6.03 | 5.96 | 6.05 | 6.43 | 6.96 | 6.81 | 6.76 | 6.69 | 6.56 |
| 5 | 8.27 | 8.19 | 8.15 | 8.13 | 8.07 | 7.99 | 7.88 | 7.94 | 8.42 | 9.09 | 8.84 | 8.75 | 8.64 | 8.47 |
| 6 | 10.18 | 10.19 | 10.22 | 10.26 | 10.22 | 10.12 | 9.98 | 10.01 | 10.59 | 11.43 | 11.06 | 10.92 | 10.74 | 10.46 |
| 7 | 12.09 | 12.22 | 12.35 | 12.47 | 12.46 | 12.38 | 12.23 | 12.24 | 12.93 | 13.94 | 13.45 | 13.27 | 13.00 | 12.58 |
| 8 | 13.83 | 14.12 | 14.42 | 14.69 | 14.77 | 14.73 | 14.57 | 14.57 | 15.39 | 16.59 | 16.01 | 15.78 | 15.44 | 14.89 |
| 9 | 15.37 | 15.82 | 16.25 | 16.63 | 16.85 | 16.92 | 16.88 | 16.96 | 17.93 | 19.32 | 18.66 | 18.39 | 17.98 | 17.31 |
| 10 | 16.81 | 17.46 | 18.04 | 18.49 | 18.79 | 18.94 | 18.95 | 19.06 | 20.18 | 21.82 | 21.22 | 20.96 | 20.56 | 19.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.224 |
| SC2 | 0 | 8 | 14.568 |
| SC3 | -18 | 7 | 12.467 |
| SC4 | -25 | 6 | 10.220 |
| SC5 | -34 | 6 | 10.196 |
| A | 1368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 1035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.