ED-240AE4-C21 C
14.85 kW
Defrost: None
Product code: ED-340AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 10,432 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 45.8 m² |
| Inner volume | 15.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 116 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-340AC7-C21 C | None |
|---|---|
| ED-340AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.04 | 6.00 | 5.98 | 5.96 | 5.91 | 5.84 | 5.76 | 5.78 | 6.12 | 6.59 | 6.39 | 6.32 | 6.21 | 6.06 |
| 5 | 7.82 | 7.90 | 7.98 | 8.04 | 8.04 | 7.98 | 7.89 | 7.91 | 8.37 | 9.02 | 8.74 | 8.64 | 8.51 | 8.30 |
| 6 | 9.58 | 9.81 | 10.02 | 10.20 | 10.26 | 10.26 | 10.20 | 10.22 | 10.82 | 11.68 | 11.31 | 11.17 | 10.97 | 10.67 |
| 7 | 11.15 | 11.55 | 11.92 | 12.27 | 12.49 | 12.62 | 12.60 | 12.65 | 13.40 | 14.47 | 14.04 | 13.88 | 13.63 | 13.24 |
| 8 | 12.51 | 13.09 | 13.63 | 14.05 | 14.37 | 14.58 | 14.70 | 14.85 | 15.77 | 17.13 | 16.75 | 16.59 | 16.36 | 15.95 |
| 9 | 13.78 | 14.56 | 15.19 | 15.83 | 16.28 | 16.57 | 16.75 | 16.94 | 18.00 | 19.55 | 19.15 | 18.97 | 18.71 | 18.26 |
| 10 | 14.94 | 15.85 | 16.76 | 17.57 | 18.14 | 18.54 | 18.79 | 19.04 | 20.24 | 22.00 | 21.57 | 21.38 | 21.08 | 20.58 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.570 |
| SC2 | 0 | 8 | 14.850 |
| SC3 | -18 | 7 | 12.368 |
| SC4 | -25 | 6 | 10.024 |
| SC5 | -34 | 6 | 9.646 |
| A | 2148 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2148 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.