ED-350AG7-C21 C
46.00 kW
Defrost: None
Product code: ED-350AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 19,926 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 204.9 m² |
| Inner volume | 43.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 228 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,040 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.1 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-350AE4-C21 C | None |
|---|---|
| ED-350AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.70 | 18.57 | 18.56 | 18.62 | 18.58 | 18.49 | 18.35 | 18.72 | 19.93 | 21.62 | 21.21 | 21.07 | 20.89 | 20.55 |
| 5 | 24.46 | 24.58 | 24.76 | 24.96 | 24.98 | 24.86 | 24.64 | 24.95 | 26.48 | 28.68 | 27.94 | 27.69 | 27.35 | 26.86 |
| 6 | 30.24 | 30.71 | 31.19 | 31.57 | 31.75 | 31.69 | 31.44 | 31.67 | 33.56 | 36.30 | 35.21 | 34.81 | 34.23 | 33.34 |
| 7 | 35.56 | 36.50 | 37.43 | 38.31 | 38.72 | 38.79 | 38.55 | 38.76 | 41.05 | 44.40 | 43.01 | 42.47 | 41.67 | 40.38 |
| 8 | 40.21 | 41.64 | 42.99 | 44.21 | 44.85 | 45.25 | 45.33 | 45.75 | 48.53 | 52.61 | 51.08 | 50.41 | 49.41 | 47.77 |
| 9 | 44.57 | 46.58 | 48.20 | 49.84 | 50.90 | 51.47 | 51.66 | 52.14 | 55.30 | 59.92 | 58.40 | 57.73 | 56.72 | 55.01 |
| 10 | 48.62 | 51.01 | 53.39 | 55.50 | 56.87 | 57.70 | 58.03 | 58.60 | 62.15 | 67.32 | 65.65 | 64.88 | 63.71 | 61.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 65.645 |
| SC2 | 0 | 8 | 45.748 |
| SC3 | -18 | 7 | 38.527 |
| SC4 | -25 | 6 | 31.185 |
| SC5 | -34 | 6 | 30.378 |
| A | 3368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 3035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.