ED-263AG7-C27 C
36.19 kW
Defrost: None
Product code: ED-350AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 21,233 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 128.8 m² |
| Inner volume | 44.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 217 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,040 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.6 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-350AE7-C21 C | None |
|---|---|
| ED-350AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.90 | 14.03 | 14.17 | 14.30 | 14.32 | 14.26 | 14.14 | 14.31 | 15.20 | 16.43 | 16.01 | 15.85 | 15.63 | 15.30 |
| 5 | 18.06 | 18.56 | 19.01 | 19.40 | 19.59 | 19.61 | 19.52 | 19.71 | 20.91 | 22.62 | 22.02 | 21.80 | 21.50 | 21.06 |
| 6 | 22.11 | 23.05 | 23.89 | 24.62 | 25.06 | 25.22 | 25.23 | 25.47 | 27.01 | 29.25 | 28.46 | 28.16 | 27.71 | 27.00 |
| 7 | 25.60 | 26.95 | 28.20 | 29.32 | 30.09 | 30.49 | 30.78 | 31.21 | 33.18 | 36.08 | 35.19 | 34.83 | 34.29 | 33.35 |
| 8 | 28.66 | 30.50 | 32.00 | 33.51 | 34.60 | 35.33 | 35.78 | 36.30 | 38.61 | 42.00 | 41.18 | 40.81 | 40.25 | 39.28 |
| 9 | 31.45 | 33.60 | 35.76 | 37.70 | 39.12 | 40.12 | 40.75 | 41.42 | 44.07 | 47.96 | 47.06 | 46.64 | 45.99 | 44.86 |
| 10 | ≈ 33.97 | 36.65 | 39.33 | 41.75 | 43.55 | 44.85 | 45.70 | 46.55 | 49.55 | 53.95 | 53.00 | 52.53 | 51.79 | 50.50 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 52.996 |
| SC2 | 0 | 8 | 36.303 |
| SC3 | -18 | 7 | 29.668 |
| SC4 | -25 | 6 | 23.892 |
| SC5 | -34 | 6 | 22.341 |
| A | 3368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 3035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.