ED-363AE4-C27 C
52.27 kW
Defrost: None
Product code: ED-350AG4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 18,423 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 273.9 m² |
| Inner volume | 59.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 263 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,040 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.7 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| ED-350AG4-C21 C | None |
|---|---|
| ED-350AG4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.23 | 20.70 | 21.17 | 21.59 | 21.81 | 21.86 | 21.77 | 22.29 | 23.76 | 25.83 | 25.31 | 25.15 | 24.93 | 24.61 |
| 5 | 25.58 | 26.50 | 27.26 | 28.04 | 28.49 | 28.66 | 28.59 | 29.05 | 30.88 | 33.52 | 32.64 | 32.31 | 31.82 | 31.07 |
| 6 | 30.39 | 31.92 | 33.32 | 34.52 | 35.27 | 35.63 | 35.60 | 36.07 | 38.28 | 41.54 | 40.37 | 39.85 | 39.14 | 37.96 |
| 7 | 34.67 | 36.76 | 38.68 | 40.37 | 41.31 | 41.99 | 42.25 | 42.86 | 45.53 | 49.44 | 48.20 | 47.62 | 46.70 | 45.14 |
| 8 | 38.49 | 41.25 | 43.48 | 45.69 | 47.25 | 48.19 | 48.64 | 49.33 | 52.39 | 56.85 | 55.48 | 54.83 | 53.83 | 52.07 |
| 9 | ≈ 41.96 | 45.09 | 48.24 | 51.04 | 53.06 | 54.33 | 54.99 | 55.81 | 59.28 | 64.31 | 62.80 | 62.05 | 60.89 | 58.83 |
| 10 | ≈ 45.07 | 48.89 | 52.73 | 56.18 | 58.72 | 60.38 | 61.30 | 62.28 | 66.17 | 71.80 | 70.16 | 69.33 | 68.02 | 65.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 70.163 |
| SC2 | 0 | 8 | 49.330 |
| SC3 | -18 | 7 | 40.664 |
| SC4 | -25 | 6 | 33.317 |
| SC5 | -34 | 6 | 30.751 |
| A | 3368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 3035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 3368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.