ED-450AE4-C21 C
63.59 kW
Defrost: None
Product code: ED-450AG4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 24,556 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 365.2 m² |
| Inner volume | 78.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 344 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.7 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| ED-450AG4-C21 C | None |
|---|---|
| ED-450AG4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 27.30 | 29.19 | 30.91 | 32.39 | 33.35 | 33.78 | 33.92 | 34.69 | 36.95 | 40.19 | 39.25 | 38.81 | 38.30 | 37.50 |
| 5 | ≈ 32.38 | 35.11 | 37.65 | 39.87 | 41.12 | 42.13 | 42.63 | 43.55 | 46.37 | 50.52 | 49.37 | 48.91 | 48.20 | 46.92 |
| 6 | ≈ 36.71 | 40.35 | 43.31 | 46.32 | 48.57 | 50.09 | 50.92 | 52.00 | 55.36 | 60.31 | 58.99 | 58.39 | 57.44 | 55.77 |
| 7 | ≈ 25.79 | ≈ 44.58 | 48.82 | 52.72 | 55.73 | 57.84 | 59.08 | 60.41 | 64.33 | 70.07 | 68.64 | 67.92 | 66.78 | 64.71 |
| 8 | not rated | ≈ 48.72 | 53.91 | 58.74 | 62.57 | 65.33 | 67.09 | 68.75 | 73.25 | 79.81 | 78.31 | 77.50 | 76.19 | 73.75 |
| 9 | not rated | ≈ 41.12 | ≈ 58.56 | 64.36 | 69.09 | 72.59 | 74.93 | 76.98 | 82.09 | 89.50 | 87.98 | 87.10 | 85.64 | 82.89 |
| 10 | not rated | ≈ 25.35 | ≈ 62.81 | 69.59 | 75.25 | 79.57 | 82.56 | 85.07 | 90.81 | 99.12 | 97.62 | 96.69 | 95.11 | 92.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 97.615 |
| SC2 | 0 | 8 | 68.748 |
| SC3 | -18 | 7 | 54.035 |
| SC4 | -25 | 6 | 43.305 |
| SC5 | -34 | 6 | 37.507 |
| A | 4368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 4035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.