ED-450AG7-C21 C
59.14 kW
Defrost: None
Product code: ED-450AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 26,557 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 273.2 m² |
| Inner volume | 58.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 297 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 84.1 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| ED-450AE4-C21 C | None |
|---|---|
| ED-450AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 26.87 | 27.57 | 28.17 | 28.67 | 28.86 | 28.81 | 28.57 | 29.01 | 30.83 | 33.38 | 32.54 | 32.26 | 31.87 | 31.30 |
| 5 | 33.54 | 34.95 | 36.19 | 37.22 | 37.77 | 37.92 | 37.71 | 38.12 | 40.44 | 43.79 | 42.51 | 42.03 | 41.30 | 40.23 |
| 6 | 39.12 | 41.21 | 43.10 | 44.50 | 45.56 | 46.17 | 46.38 | 47.00 | 49.92 | 54.21 | 52.87 | 52.34 | 51.49 | 49.97 |
| 7 | 44.14 | 46.74 | 49.34 | 51.62 | 53.19 | 54.13 | 54.54 | 55.26 | 58.70 | 63.74 | 62.18 | 61.53 | 60.53 | 58.85 |
| 8 | 47.98 | 52.09 | 55.51 | 58.53 | 60.67 | 62.00 | 62.69 | 63.59 | 67.55 | 73.34 | 71.62 | 70.85 | 69.66 | 67.61 |
| 9 | ≈ 52.44 | 57.04 | 61.35 | 65.18 | 67.93 | 69.78 | 70.81 | 71.93 | 76.44 | 83.01 | 81.16 | 80.28 | 78.92 | 76.53 |
| 10 | 56.08 | 61.59 | 66.83 | 71.53 | 75.02 | 77.43 | 78.86 | 80.25 | 85.33 | 92.71 | 90.77 | 89.80 | 88.28 | 85.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 90.767 |
| SC2 | 0 | 8 | 63.586 |
| SC3 | -18 | 7 | 52.332 |
| SC4 | -25 | 6 | 43.099 |
| SC5 | -34 | 6 | 39.618 |
| A | 4368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 4035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.