EG-330AC7-C21 C
5.63 kW
Defrost: Electric
Product code: EG-235BC7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,868 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 14.4 m² |
| Inner volume | 3.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 40 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø19 |
| EG-235BC7-C21 C | None |
|---|---|
| EG-235BC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.27 | 2.28 | 2.30 | 2.31 | 2.29 | 2.26 | 2.22 | 2.25 | 2.38 | 2.55 | 2.47 | 2.43 | 2.39 | 2.32 |
| 5 | 2.92 | 3.00 | 3.07 | 3.13 | 3.15 | 3.14 | 3.10 | 3.13 | 3.32 | 3.58 | 3.46 | 3.42 | 3.36 | 3.28 |
| 6 | 3.46 | 3.60 | 3.73 | 3.84 | 3.92 | 3.95 | 3.96 | 4.02 | 4.27 | 4.63 | 4.52 | 4.48 | 4.40 | 4.27 |
| 7 | 4.00 | 4.20 | 4.38 | 4.54 | 4.64 | 4.70 | 4.72 | 4.79 | 5.09 | 5.53 | 5.39 | 5.34 | 5.26 | 5.14 |
| 8 | 4.47 | 4.74 | 4.99 | 5.22 | 5.37 | 5.46 | 5.50 | 5.58 | 5.92 | 6.44 | 6.29 | 6.21 | 6.12 | 5.97 |
| 9 | 4.90 | 5.25 | 5.58 | 5.87 | 6.08 | 6.18 | 6.26 | 6.35 | 6.76 | 7.34 | 7.18 | 7.11 | 7.00 | 6.82 |
| 10 | 5.29 | 5.73 | 6.15 | 6.47 | 6.74 | 6.91 | 7.03 | 7.14 | 7.60 | 8.26 | 8.10 | 8.02 | 7.90 | 7.69 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.098 |
| SC2 | 0 | 8 | 5.575 |
| SC3 | -18 | 7 | 4.577 |
| SC4 | -25 | 6 | 3.731 |
| SC5 | -34 | 6 | 3.497 |
| A | 2097 mm |
|---|---|
| B | 685 mm |
| C | 310 mm |
| F | 630 mm |
| E1 | 893 mm |
| E | 1785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø19 |
| Length | 2097 mm |
|---|---|
| Width | 685 mm |
| Height | 310 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.