EG-335BC7-C21 C
8.17 kW
Defrost: None
Product code: EG-235CG7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,588 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 26.1 m² |
| Inner volume | 7.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EG-235CG7-C21 C | None |
|---|---|
| EG-235CG7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.52 | 3.55 | 3.58 | 3.61 | 3.60 | 3.57 | 3.51 | 3.61 | 3.84 | 4.17 | 4.06 | 4.02 | 3.98 | 3.93 |
| 5 | 4.43 | 4.53 | 4.62 | 4.71 | 4.73 | 4.71 | 4.65 | 4.72 | 5.01 | 5.43 | 5.24 | 5.17 | 5.08 | 4.93 |
| 6 | 5.29 | 5.48 | 5.65 | 5.80 | 5.87 | 5.88 | 5.82 | 5.89 | 6.24 | 6.76 | 6.51 | 6.41 | 6.26 | 6.02 |
| 7 | 6.05 | 6.32 | 6.57 | 6.79 | 6.93 | 6.99 | 6.97 | 7.06 | 7.49 | 8.12 | 7.82 | 7.70 | 7.51 | 7.18 |
| 8 | 6.81 | 7.16 | 7.49 | 7.76 | 7.94 | 8.03 | 8.03 | 8.14 | 8.62 | 9.33 | 9.04 | 8.91 | 8.71 | 8.36 |
| 9 | 7.47 | 7.93 | 8.36 | 8.73 | 8.96 | 9.08 | 9.10 | 9.22 | 9.77 | 10.56 | 10.24 | 10.09 | 9.85 | 9.44 |
| 10 | 8.07 | 8.65 | 9.19 | 9.64 | 9.96 | 10.13 | 10.18 | 10.31 | 10.92 | 11.81 | 11.46 | 11.29 | 11.02 | 10.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.459 |
| SC2 | 0 | 8 | 8.135 |
| SC3 | -18 | 7 | 6.856 |
| SC4 | -25 | 6 | 5.653 |
| SC5 | -34 | 6 | 5.337 |
| A | 1747 mm |
|---|---|
| B | 740 mm |
| C | 355 mm |
| F | 685 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1747 mm |
|---|---|
| Width | 740 mm |
| Height | 355 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.