EA-G-663EC4-A11 C
97.25 kW
Defrost: None
Product code: EA-G-380GG10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 56,935 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 380.9 m² |
| Inner volume | 163.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 584 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.1 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-380GG10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 26.15 | ≈ 23.83 | ≈ 23.88 | ≈ 34.71 |
| 8 | not rated | not rated | not rated | not rated | ≈ 42.56 | ≈ 64.99 | ≈ 70.81 | ≈ 77.02 |
| 10 | not rated | not rated | not rated | not rated | ≈ 91.49 | 96.86 | 102.97 | 111.83 |
| 12 | not rated | not rated | not rated | not rated | not rated | 125.51 | 133.93 | 144.82 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 23.71 | 21.16 | ≈ 21.18 | ≈ 21.08 |
| 8 | not rated | not rated | not rated | not rated | 38.13 | ≈ 35.85 | ≈ 56.77 | ≈ 63.63 |
| 10 | not rated | not rated | not rated | not rated | ≈ 52.87 | 78.59 | 84.67 | 92.51 |
| 12 | not rated | not rated | not rated | not rated | not rated | 102.41 | 110.20 | 119.64 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 96.856 | 30.41 | 88.9 |
| Low speed (Y) | 78.593 | 24.68 | 61.4 |
| A | 4315 mm |
|---|---|
| B | 1150 mm |
| C | 1430 mm |
| F | 1110 mm |
| G | 1215 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4315 mm |
|---|---|
| Width | 1150 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.